Application 2299 – Slave Mode 
Siemens Building Technologies, Inc. 
 
25 
Descriptor Address 
Application 
Description 
OVRD TIME 
20 
2281, 2283, 
2284, 2286, 
2287 
The amount of time (in hours) that the controller will operate in 
day mode, when the override switch is pressed, while the 
controller is in night mode. 
NGT OVRD 
21 
2281, 2283, 
2284, 2286, 
2287 
Indicates the mode that the controller is operating in with 
respect to the override switch. NIGHT indicates that the switch 
has not been pressed and the override timer is not active. DAY 
indicates that the switch has been pressed and the override 
timer is active. The controller then uses a day mode 
temperature setpoint. This point is only in effect when DAY.NGT 
(Point 29) indicates night mode. 
AUX.NOAUX 22  2281, 
2283, 
2284, 2286 
AUX indicates that auxiliary radiation is available. NOAUX 
indicates that auxiliary radiation is not available. 
Valid input: AUX or NOAUX 
FREE CLG 
23 
2281, 2283, 
2284, 2286, 
2287 
Point commanded by the field panel PPCL to enable or disable 
mixed air damper modulation (free cooling).  
Dl 2 
24 
2281, 2283, 
2284, 2286, 
2287, 2299 
Actual status of a contact connected to the controller at DI 2. 
ON indicates that the contact is closed; OFF indicates that the 
contact is open. If a wall switch is used, it is connected to DI 2. 
Refer to WALL SWITCH (Point 18). 
DI 3 
25 
2281, 2283, 
2284, 2286, 
2287, 2299 
Actual status of a contact connected to the controller at Al 3/Dl 
3. ON indicates that the contact is closed; OFF indicates that 
the contact is open. When a contact is connected at DI 3, Al 3 is 
not available. Refer to AUX TEMP (Point15). 
DI 4 
26 
2299 
Actual status of a contact connected to the controller. ON 
indicates that the contact is closed; OFF indicates that the 
contact is open. 
LOW TEMP DET 
26 
2281, 2283, 
2284, 2286, 
2287 
Actual status of the low temperature alarm, which is determined, 
by the current status of the low temperature detection thermostat. 
ON indicates that a low temperature has been detected. OFF 
indicates a normal condition. 
DX COOLING 
27 
2287 
YES indicates a DX coil is used in cooling mode. NO indicates a 
chilled water valve is used in cooling mode. 
Valid input: YES or NO 
ELEC.NOELEC 27 
2281, 
2283, 
2284, 2286 
Indicates whether electric heating is being used.  
Valid input: ELEC or NOELEC 
FBP.2PSVCTL 28 
2281, 
2283, 
2284, 2286 
ENABLE allows two-position valves to close when the face-
bypass damper has been closed (to full-bypass) for 2 minutes. 
DISABL disables the feature. 
Valid input: ENABLE or DISABL 
DAY.NGT 29 
2281, 
2283, 
2284, 2286, 
2287, 2299 
Indicates the mode in which the controller is operating. Day 
temperature setpoints will be used in day mode. Night 
temperature setpoints will be used in night mode. This point is 
normally set by the field panel. 
WRMUP.COOLDN 30 
2281, 
2283, 
2284, 2286, 
2287 
This point indicates whether or not the unit is currently in warm-
up/cool-down. ON indicates the unit is in warm-up/cool down. 
OFF indicates the unit is not in warm-up/cool-down.