National Instruments Field Point cFP-Al-110 ユーザーズマニュアル

ページ / 20
FieldPoint
 Operating Instructions
FP-AI-110 and cFP-AI-110
Eight-Channel, 16-Bit Analog Input Modules
These operating instructions describe how to install and use the 
FP-AI-110 and cFP-AI-110 analog input modules (referred to 
inclusively as the [c]FP-AI-110). For information about 
configuring and accessing the [c]FP-AI-110 over a network, refer 
to the user manual for the FieldPoint network module you are 
using.
Features
The [c]FP-AI-110 is a FieldPoint analog input module with the 
following features:
Eight analog voltage or current input channels
Eight voltage input ranges: 0–1 V, 0–5 V, 0–10 V, 
±60 mV, 
±300 mV, ±1 V, ±5 V,  and  ±10 V
Three current input ranges: 0–20, 4–20, and 
±20 mA
16-bit resolution
Three filter settings: 50, 60, and 500 Hz
250 V
rms
 CAT II continuous channel-to-ground isolation, 
verified by 2,300 V
rms
 dielectric withstand test
–40 to 70 °C operation
Hot swappable
Installing the FP-AI-110
The FP-AI-110 mounts on a FieldPoint terminal base (FP-TB-x), 
which provides operating power to the module. Installing the 
FP-AI-110 onto a powered terminal base does not disrupt the 
operation of the FieldPoint bank.