CAT LEHE4651-04 ユーザーズマニュアル

ページ / 8
 
AUTOMATIC TRANSFER SWITCH
 
LEHE4651-04  
 
2
 
 
 
THE CAT CTS SERIES OF AUTOMATIC 
This ruggedly built family of power contactor 
TRANSFER SWITCHES
 
switches has been specifically designed for 
 
transfer switch duty with dependability, versatility 
The Cat CTS Series power contactor  
and user friendliness of prime concern. 
Type transfer switch makes use of a fully 
programmable/configurable microprocessor-based 
controller to allow the utmost in application flexibility. 
Further, the CTS Series is offered in a wide array of 
configurations enabling it to meet the needs of even  
the most highly critical load. 
The CTS power panel components, consisting 
of power switching contacts, drive mechanism 
and terminal lugs, are mounted on a specially 
formed backplane. Logic devices including 
microprocessor control auxiliary time delays and 
special accessory equipment are assembled on 
 
the door for ease of maintenance and separation 
Available configurations include: 
from the power section. They are connected 
40-4000 Amps: 
with a numbered wiring harness equipped with 
● CTS Automatic Transfer Switches 
a disconnect plug that allows isolation of the 
● CTSD Delayed Transition Transfer Switches 
control panel for maintenance. 
 
● CTSM Manual Transfer Switches 
100-4000 Amps: 
CTS SERIES METHOD OF OPERATION 
● CTSCT Closed Transition Transfer Switches 
When the normal source fails or the voltage 
● CBTS Automatic Transfer/Bypass Switches 
drops to a predetermined point (usually 80% of 
● CBTSD Delayed Transition Bypass Switches 
nominal), if required, a circuit is closed to start 
● CBTSCT Closed Transition Bypass Switches 
the engine generator set. When the emergency 
 
source reaches 90% of rated voltage and 95% of 
All CTS products meet or exceed industry 
rated frequency, the drive solenoid is energized 
requirements to allow specification and 
through the emergency coil control relay, causing 
installation with confidence. 
the main contacts to disconnect the load from 
● UL 1008 listed through 480 VAC 
the normal source and connect it to the 
emergency source. After the drive solenoid has 
completed its electrical stroke and is seated, the 
emergency coil control relay opens to disconnect 
it. The transfer switch is now mechanically locked 
in the emergency position. When normal voltage is 
restored to a predetermined point (usually 90% of 
nominal), the control voltage sensing energizes. 
The normal side coil relay closes, and after the 
drive solenoid has completed its electrical stroke 
and is seated, the coil control relay opens to 
disconnect it. The transfer switch is now 
mechanically locked in the normal position. 
● CSA C22.2 No. 178 listed through 600 VAC 
● IEC 947-6-1 listed through 480 VAC 
● Codes and Standards 
   NFPA 70, 99, 101, 110 
   NEC 517, 700, 701, 702 
   IEEE 446, 241 
   NEMA ICS2-447 
● Controls tested in accordance with: 
   IEEE 472 (ANSI C37.90A) 
   EN55022 Class B (CISPR 22)  
   (Exceeds EN55011 & MILSTD 461 Class 3) 
   EN61000-4-2 Class B (Level 4) 
 
   EN61000-4-3 (ENV50140) 10v/m 
DRIVE MECHANISM 
   EN61000-4-4 
   EN61000-4-5, IEEE C62.41 
All CTS switches employ the simple “over-center” 
principle to achieve a mechanically locked position 
in either normal or emergency and a high speed 
drive assures contact transfer in 100 ms or less. 
High contact pressure and positive mechanical 
lock allow for high withstand and closing ratings, 
far exceeding UL requirements. 
   EN61000-4-6 (ENV50141) 
   EN61000-4-11 
● Equipment (Controls and Power Section) 
     Seismic Test Qualified to: 
       IBC-2003 
       IEEE-693-2005 
 
● Enclosures meet the requirements of: 
 
   UL 508, UL 50, ICS 6, ANSI C33.76 and 
 
   NEMA 250 
● Quality System: 
   ISO 9001 Registered