Moeller Marine XControl PLC System AWB2700-1428GB ユーザーズマニュアル

ページ / 54
12/01 AWB2700-1428GB
XC-ADP/XC-ADP-XION base 
modules
11
These functions were implemented by adapting the UPS device 
supplied by Konzept to the power supply modules of the XC600. 
When using a different UPS device, the wiring must be adapted 
accordingly.
XC-ADP/XC-ADP-XION base modules
General
A base module and a power supply module form one unit. The 
following table shows the combination possibilities of both 
modules. The modules only differ in  their capability for expansion 
with XI/ON modules.
A base module provides the platform for the other function 
modules that are fitted on. The complete unit is then fitted on the 
mounting rail.
Task of the XC-ADP-XION module
The module controls the XI/ON data bus and provides the power 
supply (5 V) to the XI/ON modules. The base module has a sepa-
rate connection for the 24 V DC field power supply of the XI/ON 
modules. It also has a C connection to which the potential for the 
C rails of the XI/ON modules can be connected.
How to expand the controller with XI/ON modules is described in 
the XI/ON manuals, ”Hardware and Engineering”, e.g. 
AWB2700-1394.
Task of the XC-ADP module
This is used as a platform for other modules.
Engineering the XC-ADP-XION base module 
Power supply for the XI/ON modules
The 24 V DC power supply required for the load supply of the XI/
ON modules is connected to the base module (
a also ”Power 
supply module”). The maximum current consumption is 10 A.
Connections
The C1 connection is routed to the XI/ON modules. It is used for 
providing an additional common potential, e.g. PE.
XI/ON modules that have a C in their designation, e.g. S4T S-B-C-
S, require the provision of a common C rail.
Figure 10:
Delayed switching of the power supply
UPS device
Base module
Power supply module
Expansion
XC-ADP
XC-POW50-UPS
XI/ON
XC-ADP-XION
XC-POW50-XION-UPS
L1
N
PE
L1
N
PE
K1T
K1T
a
XC600
Figure 11:
Connections between the XC-ADP-XION base module 
and the XI/ON modules
5 V DC from the power supply module
Data from the supply module
Field supply 24 V DC
C rail connection
Figure 12:
24 V DC and C1 connections of the XC-ADP-XION
24 V DC connection
C rail connection
Plug-in terminals, connection cross-sections:
– flexible with ferrule 0.5 mm
2
 to 2.5 mm
2
– solid 0.5 mm
2
 to 2.5 mm
2
Warning!
The maximum load on the C rail and C1 connection is 
24 V!
XI/ON modules
XC-ADP-XION
a
b
c
d
Field
Supply
24V 0V
1
1
C
1
c
a
b