Establishing the Connection 
Between PC and XC600
12/01 AWB2700-1428GB
20
Configuring the XC600
Assign the IP address and the Subnet Mask to the PLC:
X
Use the operator module to select the Network menu via MAIN 
MENU 
r DEVICE r NETWORK
X
Select menu item IP ADDRESS.
The default address 192.168.119.001 will be displayed. 
X
Change the address to 192.168.119.004.
X
Select menu item IP-MASK.
The default mask 255.255.255.000 will be displayed. Correct this 
value if a different value is shown.
Creating the connection between PC and XC600
Hardware
X
Connect the PLC with the PC, e.g. by means of a standard cross-
over Ethernet cable.
Software
Use XSoft to specify the communication parameters. The proce-
dure is described below. Further instructions are also provided in 
the chapter ”Online Communication Parameter” in the XSoft 
manual (H1347G.pdf).
The same IP address that you have assigned to the PLC 
(192.168.119.004) must now be assigned to the gateway.
Procedure:
X
In XSoft choose Online Communication Parameters.
The PC will log into the PLC. An error message will be output if the 
connection does not exist or is faulty. After the confirmation 
prompt the following window will appear:
X
Click the Gateway button.
X
Select TCP/IP as the connection and enter 192.168.119.004 as 
the address.
After confirming the entry, the address will be displayed under 
Channels in the Communication Parameters window.
X
Now set up a channel for the connection between from the 
gateway to the runtime system of the PLC.
X
Click the New button.
X
For greater clarity delete the old name and enter a text such as 
RuntimeSys.
h
The PC uses XSoft via a gateway (server) to communicate 
with the PLC runtime system of the XC600 (
a following 
figure).
Figure 33:
Connection between PC and XC600
PLC runtime system
Gateway
XC600
Runtime system
PC
Figure 34:
Communication Parameters main window
Figure 35:
Specifying the communication partners for Gateway
Figure 36:
Address displayed in the Communication Parameters 
window