Moeller Marine XControl PLC System AWB2700-1428GB ユーザーズマニュアル
12/01 AWB2700-1428GB
XC-ADP/XC-ADP-XION base
modules
modules
11
These functions were implemented by adapting the UPS device
supplied by Konzept to the power supply modules of the XC600.
When using a different UPS device, the wiring must be adapted
accordingly.
supplied by Konzept to the power supply modules of the XC600.
When using a different UPS device, the wiring must be adapted
accordingly.
XC-ADP/XC-ADP-XION base modules
General
A base module and a power supply module form one unit. The
following table shows the combination possibilities of both
modules. The modules only differ in their capability for expansion
with XI/ON modules.
following table shows the combination possibilities of both
modules. The modules only differ in their capability for expansion
with XI/ON modules.
A base module provides the platform for the other function
modules that are fitted on. The complete unit is then fitted on the
mounting rail.
modules that are fitted on. The complete unit is then fitted on the
mounting rail.
Task of the XC-ADP-XION module
The module controls the XI/ON data bus and provides the power
supply (5 V) to the XI/ON modules. The base module has a sepa-
rate connection for the 24 V DC field power supply of the XI/ON
modules. It also has a C connection to which the potential for the
C rails of the XI/ON modules can be connected.
supply (5 V) to the XI/ON modules. The base module has a sepa-
rate connection for the 24 V DC field power supply of the XI/ON
modules. It also has a C connection to which the potential for the
C rails of the XI/ON modules can be connected.
How to expand the controller with XI/ON modules is described in
the XI/ON manuals, ”Hardware and Engineering”, e.g.
AWB2700-1394.
the XI/ON manuals, ”Hardware and Engineering”, e.g.
AWB2700-1394.
Task of the XC-ADP module
This is used as a platform for other modules.
Engineering the XC-ADP-XION base module
Power supply for the XI/ON modules
The 24 V DC power supply required for the load supply of the XI/
ON modules is connected to the base module (a also ”Power
supply module”). The maximum current consumption is 10 A.
The 24 V DC power supply required for the load supply of the XI/
ON modules is connected to the base module (a also ”Power
supply module”). The maximum current consumption is 10 A.
Connections
The C1 connection is routed to the XI/ON modules. It is used for
providing an additional common potential, e.g. PE.
providing an additional common potential, e.g. PE.
XI/ON modules that have a C in their designation, e.g. S4T S-B-C-
S, require the provision of a common C rail.
S, require the provision of a common C rail.
Figure 10:
Delayed switching of the power supply
a UPS device
Base module
Power supply module
Expansion
XC-ADP
XC-POW50-UPS
XI/ON
XC-ADP-XION
XC-POW50-XION-UPS
–
L1
N
PE
PE
L1
N
PE
PE
K1T
K1T
a
XC600
Figure 11:
Connections between the XC-ADP-XION base module
and the XI/ON modules
and the XI/ON modules
a 5 V DC from the power supply module
b Data from the supply module
c Field supply 24 V DC
d C rail connection
b Data from the supply module
c Field supply 24 V DC
d C rail connection
Figure 12:
24 V DC and C1 connections of the XC-ADP-XION
a 24 V DC connection
b C rail connection
c Plug-in terminals, connection cross-sections:
b C rail connection
c Plug-in terminals, connection cross-sections:
– flexible with ferrule 0.5 mm
2
to 2.5 mm
2
– solid 0.5 mm
2
to 2.5 mm
2
Warning!
The maximum load on the C rail and C1 connection is
24 V!
The maximum load on the C rail and C1 connection is
24 V!
XI/ON modules
XC-ADP-XION
a
b
c
d
Field
Supply
24V 0V
1
1
C
1
c
a
b