Burnham Series 4S Power Flame データシート

ページ / 2
`
Burner Model
Motor
Standard UL Flame Safeguard
Gas Train
Boiler Size
Gas and 
Gas/#2 Oil
#2 Oil
HP
Voltage
Firing Sequence 
[1]
Gas
#2 Oil
Gas/#2 Oil
Size
[2]
Min. Pres. Max. Pres.
   4S-100
C3-25B
C3-OB
3
208-460/60/3
L-H-O
RM7897C/UV RM7897C/UV RM7897C/UV
2
7.3" w.c. 
14.0" w.c.
   4S-125
C4-30
C4-OA
5
208-460/60/3
L-H-O
RM7897C/UV RM7897C/UV RM7897C/UV
2
1/2
9.9" w.c. 
14.0" w.c.
   4S-150
C4-30
C4-OB
5
208-460/60/3
L-H-O
RM7897C/UV RM7897C/UV RM7897C/UV
2
1/2
13.2" w.c. 
14.0" w.c.
4S-175
C5-30
C5-O
7
1/2
208-460/60/3
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3
11.6" w.c. 
28.0" w.c.
4S-200
C6-30
C6-O
10
208-460/60/3
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3
12.8" w.c. 
28.0" w.c.
4S-250
C6-30
C6-O
10
208-460/60/3
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3
17.0" w.c. 
28.0" w.c.
   4S-300
C7-30
C7-O
15
208-460/60/3
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3
26.8" w.c. 
10 psig
   4S-350
C8-30
C8-O*
15
208-460/60/3
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3
32.4" w.c.
10 psig
4S-400
CM9B-30
CM9B-O
7
1/2
208-460/60/3
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3
40.9" w.c.
10 psig
4S-500
CM10-30
CM10-O
10
208-460/60/3
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3
63.0" w.c.
10 psig
4S-600
CM10B-30 CM10B-O
15
208-460/60/3
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3
91.0" w.c.
10 psig
4S-700
CM10C-30 CM10C-O
20
208-460/60/3
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3 / 4
90.0" w.c.
10 psig
4S-800
CM11-30
CM11C-O
25
208-460/60/3
Full Mod
RM7840L/UV RM7840L/UV RM7840L/UV
3HF
94.0" w.c.
10 psig
[1]  Explanation of Firing Sequences:
*order burner with 6" insertion depth.
Gas and Gas Sequence on Combination Gas/Oil Boilers
L-H-O
Low fire start (not proven), high fire run, air control by linkage to motorized gas valve.
Full Mod
Full modulation with proven low fire start, synchronized fuel/air control with modulating motor.
Oil and Oil Sequence on Combination Gas/Oil Boilers
L-H-O
Low fire start (not proven), high fire run, oil cylinder air control (reduced input start) with by-passing type nozzle, oil valve and oil pressure 
regulating valve. 
Full Mod
Full modulation with proven low fire start, synchronized fuel/air control with modulating motor, oil by-passing type nozzle, oil metering valve, 
oil pressure regulating valve.
[2]  Models 4S-700 - Dual size gas trains:  Leak test cock, main gas valve and auxiliary gas valve are indicated by the first number; gas regulator and main 
      shutoff cock are indicated by the second number.
11/3/06
Power Flame Burner Information
SERIES 4S