INSTALLATION - Combustible Wall Chimney Connector Pass-Throughs 
  
 
 
 
 
 
 
 
 
 
 
PAGE 13 
NOTES: 
1.  Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through 
the wall pass-through system and the chimney wall, to but not past the inner flue liner face. 
2.  A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or
a floor, or ceiling. 
3.  Where passage through a wall, or partition of combustible construction is desired, the installation shall 
conform to CAN/CSA-B365. 
 
 
 
 
 
 
Method A. 12” (304.8 mm) Clearance to Combustible Wall Mem-
ber: Using a minimum thickness 3.5” (89 mm) brick and a 5/8” 
(15.9 mm) minimum wall thickness clay liner, construct a wall 
pass-through.  The clay liner must conform to ASTM C315 (Stan-
dard Specification for Clay Fire Linings) or its equivalent. Keep a 
minimum of 12” (304.8 mm) of brick masonry between the clay 
liner and wall combustibles.  The clay liner shall run from the brick 
masonry outer surface to the inner surface of the chimney flue 
liner but not past the inner surface.  Firmly grout or cement the 
clay liner in place to the chimney flue liner.   
 
Method B. 9” (228.6 mm) Clearance to Combustible Wall Member: 
Using a 6” (152.4 mm) inside diameter, listed, factory-built Solid-
Pak chimney section with insulation of 1” (25.4 mm) or more, build 
a wall pass-through with a minimum 9” (228.6 mm) air space be-
tween the outer wall of the chimney length and wall combustibles.  
Use sheet metal supports fastened securely to wall surfaces on all 
sides, to maintain the 9” (228.6 mm) air space.  When fastening 
supports to chimney length, do not penetrate the chimney liner 
(the inside wall of the Solid-Pak chimney).  The inner end of the 
Solid-Pak chimney section shall be flush with the inside of the ma-
sonry chimney flue, and sealed with a non-water soluble refractory 
cement.  Use this cement to also seal to the brick masonry pene-
tration. 
 
Method C. 6” (152.4 mm) Clearance to Combustible Wall Mem-
ber: Starting with a minimum 24 gage (.024” [.61 mm]) 6” (152.4 
mm) metal chimney connector, and a minimum 24 gage ventilated 
wall thimble which has two air channels of 1” (25.4 mm) each, 
construct a wall pass-through. There shall be a minimum 6” 
(152.4) mm separation area containing fiberglass insulation, from 
the outer surface of the wall thimble to wall combustibles.  Support 
the wall thimble, and cover its opening with a 24-gage minimum 
sheet metal support. Maintain the 6” (152.4 mm) space.  There 
should also be a support sized to fit and hold the metal chimney 
connector. See that the supports are fastened securely to wall 
surfaces on all sides.  Make sure fasteners used to secure the 
metal chimney connector do not penetrate chimney flue liner.   
 
Method D.  2” (50.8 mm) Clearance to Combustible Wall Member: 
Start with a solid-pak listed factory built chimney section at least 
12” (304 mm) long, with insulation of 1” (25.4 mm) or more, and an 
inside diameter of 8” (2 inches [51 mm] larger than the 6” [152.4 
mm] chimney connector). Use this as a pass-through for a mini-
mum 24-gage single wall steel chimney connector. Keep solid-pak 
section concentric with and spaced 1” (25.4 mm) off the chimney 
connector by way of sheet metal support plates at both ends of 
chimney section.  Cover opening with and support chimney sec-
tion on both sides with 24 gage minimum sheet metal supports. 
See that the supports are fastened securely to wall surfaces on all 
sides. Make sure fasteners used to secure chimney section do not 
penetrate chimney flue liner. 
D
C
B
A
Min. 12 in. 
(304.8mm) 
to Combustibles
Masonry 
Chimney 
Fire Clay 
Liner 
Chimney 
Connector 
Min. Clearance 12 in. 
(304.8mm) of Brick 
Min. Chimney Clearance to Brick & 
Combustibles – 2 in. (50.8mm) 
C
h
im
ney Fl
ue 
Factory Built 
Chimney Length 
Air Space – 9 in. 
(228.6mm) Min. 
Chimney Length 
Flush with In-
side of Flue 
Min. Clearance 
9 in. (228.6mm) 
Chimney 
Connector 
Use Chimney 
Mfrs. Parts to 
Attach Connec-
tor Securely 
Solid-Insulated 
Listed Factory-
Built Chimney 
Length 
Sheet Steel Supports 
Chimney   Fl
ue 
Min. Chimney Clearance from Masonry to Sheet Steel 
Supports & Combustibles – 2 in. (50.8mm) 
Nonsoluble 
Refractory  
Cement 
Min. Chimney Clearance from Masonry to Sheet Steel 
Supports & Combustibles – 2 in. (50.8mm) 
Chimney 
Connector 
2 Air Channels, Each 1 
in. (25.4 mm) 
Min. 6 in. 
(152.4mm) glass 
Fiber Insulation 
2 Ventilated Air 
Channels, Each 
1 in. (25.4 mm) 
Construction of 
Sheet Steel 
Sheet Steel Supports 
Masonry 
Chimney 
C
h
im
ney Fl
ue 
Min. Chimney Clearance 
from Masonry to Sheet 
Steel Supports & Com-
bustibles – 2 in. 
(50 8
)
Sheet Steel 
Supports 
Chimney 
Connector 
Chimney 
Section 
Air Space – 2 in. 
(50.8mm) Min. 
Masonry 
Chimney 
Sheet  
Steel  
Supports 
Chimney 
Connector 
Chimney 
Length 
1 in. (25.4 mm) 
Air Space to 
Chimney 
Length 
Min. Clearance  
2 in. (50.8 mm)