INSTALLATION INSTRUCTIONS
FOR "WSE" SLEEVE
MOUNTING HARDWARE PROVIDED 
ITEM
 
DESCRIPTION
 
NO.
 
QTY.
 
1
 
SCREW, #12A X 2"
 
5
 
WALL PREPARATION: 
STEP 1
 
The wall opening required for a "WSE" SLEEVE is 17 1/4" high by 27 1/4" wide.
 
STEP 2
 
LINTELS must be used in opening of brick veneer and masonry walls to support the material above the "WSE" SLEEVE.
 
The following considerations should also be given:
 
A.  Adjustable SUB-BASE SB–89 or other unit support 
must be provided for panel wall type construction 
and for walls less than 8" thick. 
B.  A minimum distance of 1" must be allowed on all sides of the unit to adjacent wall and floor. Where the 
sub–base is required, the minimum distance from the floor to the sleeve must be 3 1/2". To minimize 
chances of short cycling of the compressor, the minimum clearance between the ceiling and the top of 
the unit should be 24". (See Figure 1).  
FIGURE 1 
 
Side View
INSIDE 
WALL
7/8" MINIMUM BEYOND 
INSIDE WALL
WSE SLEEVE
LINTELS
5" (127 mm)
5" (127 mm)
WALL MOUNT 
SCREW LOCATIONS
DRAIN 
EXTENSION
9/16" MINIMUM
BEYOND OUTSIDE WALL
OUTSIDE WALL
24" MINIMUM REQUIRED 
FROM TOP OF UNIT TO CEILING
1" MINIMUM
3 1/2" FOR SUBBASE
5 1/2" MAXIMUM FOR SUBBASE
 MINIMUM SPACING REQUIRED 
ON ALL SIDES OF UNIT