MODELS  MUA006A • MUA008A • MUA010A
Page 3
OUTSIDE AIR INTAKE LOCATION
Proper design and location of the outside air intake location is critical in 
ensuring that the Damper can safely and reliably provide an opening for 
fresh air to enter the home.  The following requirements for the location 
of the outside air intake must be met:
•  Outside air intake is located a minimum of 10’ from combustion ap-
pliance vents, chimneys, plumbing stacks, and bathroom or kitchen 
exhaust vents.  If local codes have more stringent separation re-
quirements, they shall apply.
•  Outside air intake is placed high enough above grade to prevent
blockage from snow or other debris such as leaves, and at a mini-
mum of 1’ above grade.
•  Make-up  air  damper  should  not  draw  air  from  crawlspaces,  ga-
rages, attics, adjacent dwelling units, or any enclosed part of the 
building.  The Damper should be installed to draw air directly from 
outdoors.
OUTSIDE AIR INTAKE OPENING PROTECTION
Because the Damper, together with the end cap and outside air duct 
which are installed with it, will allow outdoor air into the indoor environ-
ment, it is important to meet the following requirements:
•  Model AK00030 (6”), AK00032 (8”) and AK00052 (10”) fresh air inlet
wall caps include protective bird screens to keep out animals and 
outside debris. Clean screens often and do not remove.
•  If a protective bird screen other than the screen provided is used, it
must cover the entire opening of the outside air duct.  This screen 
must also have openings of at least ¼” but no larger than ½”.
•  The outdoor air intake opening should meet local code provisions
for the protection of openings in exterior walls, including steps to 
prevent moisture intrusion around the opening.  
Note that the screen over the outside air opening is not a filter.  It is 
intended to prevent the intake of leaves, animals, or debris into the out-
side air duct.  A downstream filter is necessary to remove pollen, dust, 
and other airborne particles.  Potential filter locations are shown below 
in the Typical Installations section.
MINIMUM RETURN AIR TEMPERATURE REQUIREMENTS
HVAC equipment manufacturers may have minimum requirements for 
the air temperature in the return air plenum.  Introducing outdoor air to 
the return side of the central duct system may impact this temperature.  
The installer should adjust both the size of the outside air duct and the 
location of its connection to the return side of the central duct system in 
a manner so that minimum air temperature requirements are satisfied 
under design conditions.  
PLAN THE INSTALLATION
Planning the installation first requires selecting the most appropriate 
installation approach.  The chart below offers suggestions for the most 
effective installation approach by considering a few important factors. 
Further details on the two main types of installations are provided below.
 
Yes
• House has central duct work?
Yes
• Return-air side of duct work is 
accessible -either the return-air trunk 
or return- air plenum?
Damper connected to 
return side of central 
duct system
No
No
Damper  ducted directly 
to a ceiling, floor, or wall 
register
WHAT IS INCLUDED IN THE 
PACKAGE
- Motorized Damper
- Transformer
- Pressure Switch Kit which includes:
    - Pressure Switch
    - Probe
- 12” PVC tubing 1/4” I.D.
    - Gasket
- (6) Sheet Metal Screws
TOOLS REQUIRED
- 1/4” Socket Drive
- Flathead or Phillips Screw Driver
- 3/8” Drill Bit
- Duct Tape
- Low Voltage Wire (2 Conductor)
- (2) 1/4” Female Spade Terminals
- Wire Nuts