TROUBLESHOOTING PROCEDURES FOR TEMPEST I
Issue
Cause
What to do
After installation, 
the unit doesn’t 
work.
1.  The power source is not turned ON.
1.  Make sure the circuit breaker and the unit’s 
power is ON.
2.  The power line and the cable locking connector 
is not connecting properly.
2.  Check the power connection with the unit is 
connected properly.
3.  The switch board and control board wirings are 
disconnected.
3.  Make sure the wirings between the switch 
board and control board are connected 
properly.
4.  The wires on control board are loose.
4.  Make sure the wires on the control board are 
connected properly.
5.  The switch board or control board is defective.
5.  Change the switch board or control board.
Lights work, but 
blower is not 
turning.
1.   The blower wire is not connected.
1.   Make sure the blower wire is plugged into the 
molex connector.
2.   Blower molex plug pin is not making contact.
2.   Disconnect the blower molex plug, check pins 
inside plug to see if pin is pushed inside the 
plug too far. Reseat pin if needed.
3.  The blower is defective, possible seized.
3.  Change the blower.
4.  The thermally protected system detects if the 
blower is too hot to operate and shuts the blower 
down.
4.  The blower will function properly after the 
thermally protected system cool down.
5.  Damaged capacitor.
5.  Change the capacitor.
The unit is 
vibrating.
1.  The blower is not secure in place.
1.  Tighten the blower in place.
2.  Damaged blower wheel.
2.  Change the blower.
3.  The hood is not secured in place.
3.  Check the installation of the hood.
The blower is 
working, but the 
lights are not.
1.   The light bulb plug is disconnected.
1.   Connect the light bulb plug. 
2.  Defective halogen bulb.
2.  Change the halogen bulb.
3.  The light bulb is loose.
3.  Tighten the light bulb.
The speed levels 
of the blower 
sound the same.
1.   Using the wrong size of ducting. 
1.   Change the ducting to at least 8” round or 
3-1/4”x10” rectangular for single blower or 10” 
round for dual blower. 
The hood is 
not venting out 
properly.
1.  The hood might be hanging to high from the 
cook top.
1.  Adjust the distance between the cook top and 
the bottom of the hood within 26” and 36” 
range.
2.  The wind from the opened windows or opened 
doors in the surrounding area are affecting the 
ventilation of the hood.
2.  Close all the windows and doors to eliminate 
WKHRXWVLGHZLQGÀRZ
3.  Blockage in the duct opening or duct work.
3.  Remove all the blocking from the duct work or 
duct opening.
4.  The direction of duct opening is against the wind.
4.  Adjust the duct opening direction.
5.  Using the wrong size of ducting.
5.  Change the ducting to correct size.
0HWDO¿OWHULV
vibrating.
 0HWDO¿OWHULVORRVH
 &KDQJHWKHPHWDO¿OWHU
2.  Spring clip is broken.
2.  Change the spring clip.
RF Remote 
control does not 
work.
1.   Battery is dead.
1.   Replace the battery with type A23 12v.
2.   Poor communication with the hood.
2.   Remote must be within 15 feet of the hood.
3.   RF remote lost communication with the hood.
3.   Reset the hood and remote by switching the 
power off at the circuit breaker for 5 minutes. 
Perform remote synchronization process on 
page 18.
The blower turns 
on by itself.
1.   The clean air function has been enabled turning 
the blower on every 4 hours. 
1.   Disable the clean air function by following the 
steps on page 17.