OceanAire 2OACH2412 操作ガイド

ページ / 36
Cooling Capacity Total  95° F at 60% RH 
   Outdoor high fan speed. 
Amps & Watts at 208 Volts 
CFM with free discharge Hi/Low fan speed 
Time delay fuses/circuit breakers are recommended 
EER determined with condenser discharge air ducted into another area on high fan speed 
Sound pressure, dB at 5 feet, commercial configuration (ducted condenser air), hi/low 
    evaporator fan speed. 
MODEL 
2OAC1211  2OAC1811  2OAC2412  2OAC3612  2OAC3632  2OAC6012  2OAC6032 
2OAC6034 
Cooling Capacity1 
13,500 
16,500 
23,500 
36,000 
36,000 
60,000 
60,000 
60,000 
Voltage 
 
 
 
 
208/230/3 
208/230/1 
208/230/3 
460/3 
Cooling Amps2 
11.2/5.6 
12.5/6.2 
12.3 
19.5 
12 
40.0 
22.0 
11.4 
Cooling Watts2 
1250 
1440 
2200 
3360 
3360 
4992 
4992 
4992 
E.E.R.5 
12.0 
11.5 
10.9 
10.7 
10.7 
12.0 
12.0 
12.0 
In Rush Current (AMPS) 
92.8 
114.2 
79 
128.8 
111.8 
198.0 
134.2 
135.6 
Fuse/Breaker (Amps)4 
15 
15 
20 
30 
20 
50 
40 
30 
Plug Type 
5-15P 
5-15P 
6-20P 
6-30P 
L15-20P 
6-50P 
L15-30P 
L16-30P 
Compressor HP 
1 1/2 
Compressor RLA 
9.3 
11.4 
8.3 
17.9 
11.4 
28.0 
20.0 
8.2 
Compressor LRA 
58 
65 
49 
88 
77 
169 
123 
59.6 
Evap CFMe Hi/Low 
400/340 
600/500 
810/680 
1310/1100 
1310/1100 
2000/1600 
2000/1600 
2000/1600 
Evap Motor HP 
1/17 
1/14 
1/7 
1/3 
1/3 
1/2 
1/2 
1/2 
Evap Motor Watts 
50 
59 
125 
260 
260 
365 
365 
365 
Condenser CFM3 
600 
930 
1100 
1800 
1800 
3000 
3000 
3000 
Condenser Motor HP 
1/14 
1/8 
1/5 
1/2 
1/2 
3/4 
3/4 
3/4 
Condenser Motor Watts 
59 
106 
160 
365 
365 
570 
570 
570 
Condensate Pump Head 
20 Feet 
 
 
 
 
 
 
 
 
Sound Level6 Hi/Low 
56/54 
61/60 
64/62 
 
 
 
 
 
R-22 Charge Oz. 
29 
36 
40 
 
 
 
 
 
Height with Casters 
36 1/2 
 
 
 
 
 
 
 
Height without Casters 
32 1/2 
 
 
 
 
 
 
 
Width 
20 
 
 
 
 
 
 
 
Depth 
25 
 
 
 
 
 
 
 
Net Weight 
180 
245 
230 
350 
 
350
 
470
 
470
 
490 
Shipping Weight 
200 
285 
260 
390 
 
390
 
520
 
520
 
550 
Shipping Volume 
18 
34 
34 
37 
 
37
 
40
 
40
 
40 
Electrical ratings per U.L 484 at 95°F DB/75°WB on high fan speed 
 
Pump Optional on these units 
Specifications subject to change without notice. 
115/60/1 or 208/230/1 
45 
77 
66/64 
65/63 
48 1/2
 
52 1/2 
39 1/2 
44
 
 48 
28 
              30
 
39 
208/230/1 
24  
35 
 
Pump Standard on 5-Ton 
Ambient operating range 65° to 105° 
May operate to 55° if equipped with optional factory  
Installed hot gas bypass 
44 1/2