                                                       STANDARD FEATURES 
SERVICEABILITY 
 
All AquaCooler Series units are designed with removable panels to provide full service accessibility. 
Turn to page 11 “Part Replacement Procedure” for removal of the correct panel when replacing a part.  
 
AUTOMATIC WATER VALVE 
 
All units are equipped with a direct-acting, refrigeration system head pressure actuated water regulating 
valve. This valve, factory set for 94° - 100° leaving water temperature (LWT), flows only the amount of 
water required to achieve the desired refrigeration system operating pressure. Units used for closed loop 
operation may be ordered without the water valve. If, however, the temperature of the return water is 
questionable in a closed loop, the water valve may be helpful and left in the system with little pressure 
drop. 
 
ATTRACTIVE CABINET 
 
The AquaCooler Series cabinet is constructed of 18 gauge galvanized steel with a platinum texture poly-
ester powder coated finish that will compliment any decor. The entire cabinet is insulated with a sound 
absorbent insulation for cool, quiet comfort. The base pan is 14 gauge galvanized steel and remains dry 
and free from odor and fungal growth. 
 
HIGH PRESSURE SAFETY SWITCH 
 
All units incorporate a manual re-set high pressure switch for maximum protection of the refrigeration 
system and compressor. The cut-out pressure setting is 375 ± 5 PSIG for all models except OWC36 
which uses 425± 5 PSIG. If the pressure exceeds this setting, the compressor stops and can be re-started 
by depressing the “RESET” button located on the back panel of the unit. The high pressure control’s cap-
illary line is attached to a schrader valve. This allows replacement of a defective control without recover-
ing the refrigerant. 
High Pressure Switch Re-
set Button 
 
 Water Cooled Condenser 
 
Power Cord 
 
Caster 
Compressor 
 
Electrical Box 
 
Control Board