Zephyr CCAE36ASX マニュアル

ページ / 22
5
Duct pieces
Total
Equivalent number
length x used     =
3-1/ 4” x 10”
Rect.,
straight
1 Ft.           x (     ) =
Ft.
8” Round,
straight
1 Ft.           x (     ) =
Ft.
3-1/ 4” x 10”
Rect.90
0
elbow
15 Ft.         x (     ) =
Ft.
3-1/ 4” x 10”
Rect.45
0
elbow
9 Ft.           x (     ) =
Ft.
3-1/ 4” x 10”
Rect.90
0
flat elbow
24 Ft.         x (     ) =
Ft.
3-1/ 4” x 10”
Rect.
wall cap
with damper
30 Ft.         x (     ) =
Ft.
3-1/ 4” x 10”
Rect.to
6” round
transition
5 Ft.           x (     ) =
Ft.
3-1/ 4” x 10”
Rect.to
6” round
transition
90
0
elbow
15 Ft.         x (     ) =
Ft.
6” Round,
90
0
elbow
15 Ft.         x (     ) =
Ft.
6” Round,
45
0
elbow
9 Ft.           x (     ) =
Ft.
Ft.
7” Round,
straight
1 Ft.           x (     ) =
Ft.
Subtotal column 1 =
Duct pieces
Total
Equivalent number
length x used     =
6”- 8” Round
wall cap
with damper
30 Ft.         x (     ) =
Ft.
Round
wall cap
with damper
30 Ft.         x (     ) =
Ft.
7” or 8”
Round,
90
0
elbow
15 Ft.         x (     ) =
Ft.
7” or 8” 
7” or 8” 
Round,
45
0
elbow
9 Ft.           x (     ) =
Ft.
Ft.
Ft.
Ft.
6”- 8” Round,
roof cap
30 Ft.         x (     ) =
Ft.
7” or 8”
Round,
roof cap
30 Ft.         x (     ) =
Ft.
Subtotal column 2 =
Subtotal column 1 =
Total ductwork      =
Maximum Duct Length:
For satisfactory air movement,
the total duct length of a 3 1/ 4” x 10” rectangular 6”, 7” or 8”
diameter round duct should not exceed 100 equivalent feet.
6” round to
3-1/ 4” x 10”
rect.
transition
1 Ft.           x (     ) =
Ft.
6” round to
3-1/ 4” x 10”
rect.
transition
90
0
elbow
16 Ft.         x (     ) =
Ft.
7” round to
3 1/ 4” x 10”
rect.
transition
8 Ft.           x (     ) =
Ft.
7” round to
3-1/ 4” x 10”
rect.
transition
90
0
elbow
15 Ft.         x (     ) =
Ft.
Installation – 
Ducting Calculation Sheet