Zephyr AK8800AG オーナーマニュアル

ページ / 17
14
www.zephyronline.com
T
roubleshooting
TROUBLESHOOTING PROCEDURES FOR WILLOW
Issue
Cause
What to do
After installation, 
the unit doesn’t 
work.
1.  The power source is not turned ON.
1.  Make sure the circuit breaker and the unit’s 
power is ON.
2.  The power line and the cable locking connector 
is not connecting properly.
2.  Check the power connection with the unit is 
connected properly.
3.  The switch board and control board wirings are 
disconnected.
3.  Make sure the wirings between the switch 
board and control board are connected 
properly.
4.  The wires on control board are loose.
4.  Make sure the wires on the control board are 
connected properly.
5.  The switch board or control board is defective.
5.  Change the switch board or control board.
Light works, 
but motor is not 
turning.
1.  The motor is defective, possible seized.
1.  Change the motor.
2.  The thermally protected system detects if the 
motor is too hot to operate and shuts the motor 
down.
2.  The motor will function properly after the 
thermally protected system cool down.
3.  Damaged capacitor.
3.  Change the capacitor.
4.  The motor wire is not connected.
4.  Make sure the motor wire is plugged into the 
molex connector.
The unit is 
vibrating.
1.  The motor is not secure in place.
1.  Tighten the motor in place.
2.  Damaged blower wheel.
2.  Change the blower.
3.  The hood is not secured in place.
3.  Check the installation of the hood.
The motor is 
working, but the 
lights are not.
1.  Defective halogen bulb.
1.  Change the halogen bulb.
2.  The light bulb is loose.
2.  Tighten the light bulb.
3.  The wires on the control board are loose.
3.  Make sure the wires on control board are 
connected properly.
The hood is 
not venting out 
properly.
1.  The hood might be hanging too high from the 
cook top.
1.  Adjust the distance between the cook top and 
the bottom of the hood within 26” and 36” 
range.
2.  The wind from the opened windows or opened 
doors in the surrounding area are affecting the 
ventilation of the hood.
2.  Close all the windows and doors to eliminate 
the outside wind fl ow.
3.  Blockage in the duct opening or duct work.
3.  Remove all the blocking from the duct work or 
duct opening.
4.  The direction of duct opening is against the wind.
4.  Adjust the duct opening direction.
5.  Using the wrong size of ducting.
5.  Change the ducting to correct size.
Metal fi lter is 
vibrating.
1. Metal 
fi lter is loose.
1.  Change the metal fi lter.
2.  Spring clip is broken.(baffl e fi lter)
2.  Change the spring clip.
RF Remote 
control does not 
work
1.  Battery is dead
1.  Replace battery with type A23 12v
2.  Poor communication with the power pack
2.  Remote control must be within 15 ft of power 
pack
3.  RF remote lost communication with power pack
3.  Reset power pack and remote by switching 
power off at the circuit breaker for 5 minutes. 
Pace remote on counter top near power pack 
and switch the circuit breaker back on.