Operation Section
28
(1) How to re-start the unit
• If the LCD indicates “PROGRAM ON”, press the COOL ON/OFF button to continue running the
program. If the LCD indicates “PROGRAM ON” continuously (program activated), no further
steps are necessary. If no program exists or the program was deactivated, press the FAN MODE
button or the COOL ON/OFF button. The unit returns to the previous temperature set point.
6.9 Condensate Pump Kit (optional)
• The Classic Plus 14 model comes standard with a drain tank, which collect the water that forms
on the evaporator during normal cooling operation. If the unit is required to operate continuously
without periodic emptying of this tank, a condensate pump may be needed. A condensate pump
kit is available for the Classic Plus 14 model.
6.10 Automatic Restart after Power Interruption
• The program within the microprocessor of the Classic Plus 14 contains a feature that
automatically restarts the unit after power is lost and then regained. The unit also has memory
in order to return itself back to the operating mode (either manual or preset program) it was in
prior to the loss of power. All preset programs are retained in the memory in the event power
loss occurs.
6.11 Compressor Protection
• There is a time delay program within the microprocessor. This prevents a heavy load from being
applied on the compressor motor when restarting the unit cool mode after a very short period of
time. This delay is in effect any time when the compressor is turned on by either the COOL
ON/OFF button, temperature set point (thermostatic control), power interruption restart or
condensate pump (optional) operation.
Specifications:
Time delay
- 120 ± 20 sec.
6.12 Temperature Control
• The compressor operation cool mode is controlled by the microprocessor which receives input
signals from the room temperature thermistor (evaporator inlet air) and the setting of the
temperature set point. The temperature set point (desired room temperature) can be adjusted
by pressing the 
U/V buttons on the control panel. The adjustment range of the temperature set
point is 70 °F to 95 °F (21 °C to 35 °C).