Repair Section
51
8.7 Inspection of Fan Motor
• Measure resistance across the terminals of the
fan motor. (All terminals must be disconnected
from the unit.)
• Between terminals (at 77 °F (25 °C))
- J6-CF1 Approx. 7.6 ohm
- J6-CF2 Approx. 27.7 ohm
- CF1-CF2 Approx. 35.5 ohm
• If the measured resistance is not equal to these
standard values, replace the fan motor.
8.8 Inspection of Compressor Motor
• Measure resistance across the terminals of the
compressor motor. (All terminals must be
disconnected from the unit.)
• Between terminals (at 77 °F (25 °C))
- R-C Approx. 0.7 ohm
- C-S Approx. 2.2 ohm
- S-R Approx. 2.9 ohm
• If the measured resistance is not equal to these
standard values, replace the compressor. The
overload relay is internal to the compressor.
8.9 Inspection of Wiring Connection
• Refer to the Wiring Diagrams on page 21 and check for connection of each wire.
8.10 Inspection of Thermistor
• Using an Ohm-meter, check the resistance value across the 2-pin connector. At normal
temperature (77 °F (25 °C)) either thermistor (room or freeze) should measure approximately
10k ohm.