OceanAire 2OACH3634 マニュアル

ページ / 36
ConvertibleAire
Deluxe Air-Cooled Portable Heat Pumps
Specifcations subject to change without notice
Note: Condenser inlet air plenum adds 
13 inches to dimension “C”
D
B
A
C
MODEL: 2OACH 1211 1811 2412
3612
3632
3634 6012
6032
6034
Cooling Capacity 
1
11,800 16,800
24,020
36,050
36,050
36,050
60,050
60,050
60,050
Voltage (V/Phase) at 60Hz
115/1 
208-230/1 208-230/1 208-230/3 460/3
208-230/1 208-230/3 460/3
Cooling Amps 
6
10.4
14.1
14.9
18.1
17.2
8.7
32.0
20.4
14.8
Cooling Watts 
6
1180
1670
2700
3620
3620
3620
6000
6000
6000
In Rush Current (Amps)
77.5
100.5
90
140
122
122
169
140
140
Plug Type
5-15P
5-20P
6-20P
6-30P
L15-30P
L16-20P 6-50P
L15-30P
L16-20P
EER 
3
10.0
10.0
8.9
10.0
10.0
10.0
10.0
10.0
10.0
Compressor HP
1
1 1/2
2
3
3
3
5
5
5
Compressor RLA
9.5
12.3
10.5
13.6
8.8
5.0
27.6
18.1
9.0
Compressor LRA
50
63
48
83
77
35
158
137
62
Evap CFM 
4
400
600
810
1310
1310
1310
1950
1950
1950
Evap Motor HP
1/8
1/8
1/3
1/3
1/3
1/3
1
1
1
Evap Motor Watts
200
210
350
375
375
375
550
550
550
Condenser CFM
580
930
1010
1390
1390
1390
2200
2200
2200
Condenser Motor HP
1/8
1/8
1/3
1
1
1
1
1
1
Condenser Motor Watts
280
450
330
460
460
460
750
750
750
Condensate 
5 Gallon Condensate Tank - STANDARD (Pump Optional)   
Pump -STANDARD (20 ft. Lift)
Sound Level 
5
54
60
65
69
78
R-410A Charge Oz.
18
40
37
66
80
(A)  Height with Casters (in.)
36 1/2
44 1/2
50 1/4
52 1/4
(B)  Width (in.)
20 
24 
28 
(C)  Depth (in.)
25
30
35
39
(D)  Height w/o Casters (in.)
32 1/2
39 1/2
45
46 
Net Weight (lb.)
180
260
260
365
485
485
515
Shipping Weight (lb.)
200
285
285
405
525
525
555
Shipping Volume (cu. ft.)
19
28
40
48
380
420
SPECIFICATIONS
1.  Cooling Capacity is total BTUH at 80ºDB/67ºWB return
    air, 95ºF Outdoor at high fan speed.  Heating capacity
     is total BTUH at 70ºF DB/60ºF WB (Indoor), 
     47ºF DB/43ºF WB (Outdoor)
2.  Time Delay fuses/circuit breakers are recommended
3.  EER is determined at high fan speed, with condenser   
     discharge air ducted into another area
4.  CFM with free discharge
5.  Sound Pressure, dB at 5 feet, commercial operation
6.  Amps & Watts at 208 Volts
May operate down to 55º if equipped with hot gas bypass 
(Factory installed)
Ambient operating range 65º to 105º
50 Hz MODELS AVAILABLE - CONSULT FACTORY
Heating Capacity 
1
11,800
16,800
24,020
36,050
36,050
36,050
60,050
60,050
60,050