SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric 
power input in watt-hours during the same period.
COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat but excluding supple-
mentary resistance (BGU’s per hour) divided by the total electric input (watts) x 3.412.
FIGURE 1 - UNIT CUT AWAY
DIRECT DRIVE
CONDENSER
FAN MOTOR
HIGHLY EFFICIENT ENHANCED
COPPER TUBE/ALUMINUM FIN
INDOOR COIL
HIGHLY EFFICIENT
ENHANCED COPPER
TUBE/ALUMINUM FIN
OUTDOOR COIL
DECORATIVE
PROTECTIVE
COIL GUARD
ECM DIRECT DRIVE
BLOWER MOTOR WITH
SLIDE-OUT BLOWER ASSEMBLY
HEAVY GAUGE
REMOVABLE
BASE RAILS
HIGH-EFFICIENCY
COMPRESSOR
RIGIDLY
MOUNTED
LONG-LASTING
POWDER PAINT
FINISH
LOW  VOLTAGE
TERMINAL BLOCK
HIGH VOLTAGE
TERMINAL BLOCK
BACK AND BOTTOM
RETURN AIR
AND SUPPLY AIR
DUCT OPENING
TABLE 1:  RATINGS
MODEL 
BHP
COOLING CAPACITY
1
80 / 67-95°F
HSPF
SOUND
RATING
2
(dbels)
NET HEATING CAPACITY
AVAILABLE ELECTRIC HEAT
NOMINAL CAPACITY KW
@47°F
@17°F
MBH
SEER
EER
MBH
COP
MBH
COP
SINGLE PHASE
THREE PHASE
024
24.4
13.0
11.3
7.6
79
21.8
3.40
11.0
2.00
5.0, 7.5, 10.0
N / A
030
30.0
13.0
11.3
7.6
77
28.2
3.40
16.5
2.20
5.0, 7.5, 10.0, 15.0
10.0, 15.0
036
35.5
13.0
11.3
7.6
77
32.0
3.30
18.9
2.20
5.0, 7.5, 10.0, 15.0
10.0, 15.0
042
42.0
13.0
11.3
7.6
83
42.0
3.40
23.0
2.20
10.0, 15.0
10.0, 15.0
048
47.0
13.0
11.3
7.6
82
45.0
3.30
25.8
2.20
10.0, 15.0, 20.0, 25.0
10.0, 15.0, 20.0, 25.0
1.
Certified in accordance with the Uniary Small Equipment certification program, which is based on ARI Standard 210/240.
2.
Rated in accordance with ARI Standard 270.
TABLE 2: PHYSICAL DATA
MODELS
BHP
024
030
036
042
048
INDOOR
BLOWER
CENTRIFUGAL BLOWER (Dia. x Wd. in.)
FAN MOTOR HP (ECM)
10 X 8
1/2
10 X 8
1/2
11 x 10
3/4
11 x 10
3/4
11 X 10
3/4
INDOOR
COIL
ROWS DEEP
FINS PER INCH
FACE AREA (Sq. Ft.)
2
15
4.38
3
13
4.38
3
15
4.38
3
16
5.63
3
16
5.63
OUTDOOR
FAN
PROPELLER DIA. (in.)
FAN MOTOR HP
NOM. CFM TOTAL
22
1/4
1,800
22
1/4
1,800
22
1/4
2,400
22
1/4
2,400
22
1/4
3,000
OUTDOOR
COIL
ROWS DEEP
FINS PER INCH
FACE AREA (Sq. Ft.)
1
20
11.7
1
20
11.7
2
20
11.7
2
20
16.4
2
20
16.4
CHARGE
REFRIGERANT 22 (lbs./oz.)
5 / 5
5 / 15
8 / 4
9 / 14
12 / 0
FILTER
FACE AREA (Sq. Ft. / Qty. / Size)
4.28 / 2 / 14 x 22
COMPRESSOR
Hermetic Type, Qty. = 1
Reciprocating
Scroll
Scroll
Scroll
Scroll