Control Valve Selection Criteria
2-Way
Unitary
Globe
Fan Coil
Cartridge 
Cage
Cartridge 
Globe
Threaded
Flanged
Attribute
Specification
VU52
VU53
VCzA/B
V58x2
V5011N...
V5011F
V5011G
V5011A
V5011B
VGF2xS
Pipe Size
 
1/2"  [DN15]
  
3/4"  [DN20]
 
1"  [DN25]
 
1 1/4"  [DN32]
 
1 1/2"  [DN40]
 
2"  [DN50]
 
2 1/2"  [DN65]
 
3"  [DN80]
 
4"  [DN100]
 
5"  [DN125]
 
6"  [DN150]
 
 Other  (maximum size)
Pipe Fittings
Sweat
NPT Internal Thread
Inverted Flare
ANSI Flange
Static Pressure 
ANSI 125/150
ANSI 250/300
Other
300 psi
300 psi
230 psi
Media
Chilled Water
Hot Water
Low Pressure Steam
N1, N3
High Pressure Steam
N2
Flow Capacity, Cv
Multiple ratings per pipe size
One rating/size above 1/2"
Valve Action
Direct Acting ****
N1, N2
Reverse Acting *****
N3
Rotary N.O.
Rotary N.C.
Flow Characteristic
Equal Percentage
Modified Equal Percentage
Linear
Quick Open
Close-off  
pressure***
 
High** 
(100 psid minimum)
 
Medium  (40 psid minimum)
 
Varies with actuator
Maximum Seat 
Leakage
ANSI Class III (0.10% Cv max.)
0.02%
0.05%
ANSI Class IV (0.01% Cv max.)
Bubble-tight design
Other (see product data literature)
33 mL/m
0.5%
0.5%
Rangeability
 
High 
(50:1 minimum)
N/A
 
Medium*  (15~50:1)
 
Low 
(under 15:1)
Trim
Brass, plated brass, bronze
N3
Brass plug /Stainless seat
N1
Stainless Steel
N2
Resilient materials
In-line  
Serviceability
Cartridge
Packing
Rebuild
Actuation Options
Electronic Modulating
Tri-state floating
Pulse Width Modulation
2-position low voltage
o
2-position line voltage
Electric Spring Return
Electronic Fail Safe
Pneumatic, low pressure
Pnuematic bidirectional (Hi-Pr)
Pnuematic spring return (Hi-Pr)
Notes 
* Best used with supply water reset from outdoor air temperature.
 
** Can dead-head pumps.  Use with VFD-controlled pumps with maximum pressure cut-out
 
*** Maximum operating differential pressure.  Static close-off pressure may be higher. Maximum pressure for quiet service may be less.
 
**** Stem down to close
 
***** Stem up to close