Honeywell MS4103 ユーザーズマニュアル
24
Cartridge Cage Valves
Non-Fail Safe
Actuator O.S. Number
VC6834ZZ11 VC6934ZZ11 VC7934ZZ11 VC4011ZZ11 VC4013ZZ11 VC8114ZZ11 VC8714ZZ11
Power Supply
Voltage
24 Vac
24 Vac
24 Vac
100-130 Vac 200-240 Vac
24 Vac
24 Vac
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
60 Hz
60 Hz
Power
6 VA
6 VA
6 VA
6 VA
6 VA
6 VA
6 VA
Control
2-10 Vdc
•
4-20 mA (external 500 Ohm resistor)
•
Floating
•
•
2-Position SPDT
•
•
2-Position SPST
•
•
•
•
Pulse Width Modulation
Aux Switch
SPDT Class II
2.2 A
2.2 A
Fail Safe Action
Stay in Place Stay in Place Stay in Place Stay in Place Stay in Place Stay in Place Stay in Place
Reversible Operation
Wiring Change
•
•
DIP Switch
Stroke Timing
Seconds @ 60 Hz (Drive)
120
120
120
6
6
6
6
Fail Safe
Electrical Connection
Cable length, in.
60
60
60
39.4
39.4
60
60
Plenum-rated cable
•
•
•
•
•
1/2 in. flexible conduit adapter
•
•
•
•
•
Valve Size
(inches)
Connection
Type
Flow Capacity
(Cv)
Flow
Characteristic
Valve O.S. Number
2-W
ay
1/2"
f NPT
0.7
Modified Equal %
VCZBB3500 VCZBB3500 VCZBB3500
Sweat
0.7
VCZAA3500 VCZAA3500 VCZAA3500
f NPT
1.3
VCZBB3600 VCZBB3600 VCZBB3600
Sweat
1.3
VCZAA3600 VCZAA3600 VCZAA3600
Sweat
1.9
VCZAA3800 VCZAA3800 VCZAA3800
f NPT
1.9
VCZBB3800 VCZBB3800 VCZBB3800
Sweat
2.3
VCZAA3400 VCZAA3400 VCZAA3400
f NPT
2.3
VCZBB3400 VCZBB3400 VCZBB3400
f NPT
3.5
Linear
VCZBB3100 VCZBB3100 VCZBB3100 VCZBB1100 VCZBB1100 VCZBB1100 VCZBB1100
Sweat
3.5
Linear
VCZAA3100 VCZAA3100 VCZAA3100 VCZAA1100 VCZAA1100 VCZAA1100 VCZAA1100
3/4"
f NPT
3.9
Modified Equal %
VCZAL3400
VCZAL3400
VCZAL3400
Sweat
3.9
Modified Equal %
VCZAM3400 VCZAM3400 VCZAM3400
f NPT
4.7
Linear
VCZAL3100
VCZAL3100
VCZAL3100
VCZAL1100
VCZAL1100
VCZAL1100
VCZAL1100
Sweat
4.7
Linear
VCZAM3100 VCZAM3100 VCZAM3100 VCZAM1100 VCZAM1100 VCZAM1100 VCZAM1100
1"
f NPT
4.2
Modified Equal %
VCZAR3400 VCZAR3400 VCZAR3400
Sweat
4.2
Modified Equal %
VCZAS3400 VCZAS3400 VCZAS3400
f NPT
6.6
Linear
VCZAR3100 VCZAR3100 VCZAR3100 VCZAR1100 VCZAR1100 VCZAR1100 VCZAR1100
Sweat
6.6
VCZAS3100 VCZAS3100 VCZAS3100 VCZAS1100 VCZAS1100 VCZAS1100 VCZAS1100
1-1/4"
f NPT
7
VCZBD3100 VCZBD3100 VCZBD3100 VCZBD1100 VCZBD1100 VCZBD1100 VCZBD1100
Sweat
7
VCZBE3100 VCZBE3100 VCZBE3100 VCZBE1100 VCZBE1100 VCZBE1100 VCZBE1100
Valve Size
(inches)
Connection
Type
Flow Capacity
(Cv)
Flow
Characteristic
Valve O.S. Number
3-W
ay Mixing/ Diverting
1/2"
f NPT
0.7
Modified Equal %
VCZNB7500 VCZNB7500 VCZNB7500
Sweat
0.7
VCZMA7500 VCZMA7500 VCZMA7500
f NPT
1.5
VCZNB7600 VCZNB7600 VCZNB7600
Sweat
1.5
VCZMA7600 VCZMA7600 VCZMA7600
f NPT
1.5
VCZNB7800 VCZNB7800 VCZNB7800
Sweat
1.5
VCZMA7800 VCZMA7800 VCZMA7800
f NPT
2.7
VCZNB7400 VCZNB7400 VCZNB7400
Sweat
2.7
VCZMA7400 VCZMA7400 VCZMA7400
f NPT
3.7
Linear
VCZNB7100 VCZNB7100 VCZNB7100 VCZNB6100 VCZNB6100 VCZNB6100 VCZNB6100
Sweat
3.7
Linear
VCZMA7100 VCZMA7100 VCZMA7100 VCZMA6100 VCZMA6100 VCZMA6100 VCZMA6100
3/4"
f NPT
4.2
Modified Equal %
VCZMK7400 VCZMK7400 VCZMK7400
Sweat
4.2
Modified Equal %
VCZML7400 VCZML7400 VCZML7400
f NPT
6.6
Linear
VCZMK7100 VCZMK7100 VCZMK7100 VCZMK6100 VCZMK6100 VCZMK6100 VCZMK6100
Sweat
6.6
VCZML7100 VCZML7100 VCZML7100 VCZML6100 VCZML6100 VCZML6100 VCZML6100
1"
f NPT
8.3
VCZMR7100 VCZMR7100 VCZMR7100 VCZMR6100 VCZMR6100 VCZMR6100 VCZMR6100
Sweat
8.3
VCZMS7100 VCZMS7100 VCZMS7100 VCZMS6100 VCZMS6100 VCZMS6100 VCZMS6100
1-1/4"
f NPT
9
VCZND7100 VCZND7100 VCZND7100 VCZND6100 VCZND6100 VCZND6100 VCZND6100
Sweat
9
VCZNE7100 VCZNE7100 VCZNE7100 VCZNE6100 VCZNE6100 VCZNE6100 VCZNE6100
Honeywell Cartridge Cage Valves family (VC Series) are highly serviceable
and completely rebuildable.
and completely rebuildable.
Select from 2-position (both low and line voltage), floating, and modulating
actuators, and fail-safe actuators with configurable open/closed
functionality on power failure depending on the application. Since these
valves are not sensitive to flow direction; they can do both mixing and
diverting without changing anything except the piping.
actuators, and fail-safe actuators with configurable open/closed
functionality on power failure depending on the application. Since these
valves are not sensitive to flow direction; they can do both mixing and
diverting without changing anything except the piping.