Honeywell MS4103 ユーザーズマニュアル

ページ / 268
64
Actuator Features
Without Positive 
Positioner
With Positive  
Positioner
Actuator  .S. Number
MP953C1471
MP953C1489
MP953C1547
MP953E1285
MP953E1400
MP953E1418
Diaphragm
13"
13"
8"
8"
13"
13"
Action
DA
DA
DA
DA
DA
DA
Spring Range
2-7psi 4-11psi 3-15psi 4-11psi
4-11psi
4-11psi
Positioner Span
n/a
n/a
n/a
5psi range 5psi range 10psi range
Stroke
1-1/2" 1-1/2" 1-1/2"
1-1/2"
1-1/2"
1-1/2"
Valve Size 
(inches)
Cv
Valve  
Type
Max Static  
Water Pressure
ANSI 
Class
Max Steam  
Pressure
Flow  
Characteristic
Valve  
Action
Valve OS  
Number
Close-off Pressure -
See Charts On Page 57
2-W
ay W
ater & Steam V
alves
4"
160
Standard
250 psi
125
15 psi (2-position)
Equal %
Stem down to close
V5011A1858
V*-NO
V*-NO
V*-NO
V**-NO
V**-NO
V**-NO
160
Standard
250 psi
15 psi (2-position)
Stem up to close
V5011B1013
W*-NO W*-NO W*-NO W**-NO
W**-NO
W**-NO
150
Pressure Balanced
175 psi
125 psig / 353 F 
Stem down to close
VGF21EP40
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
150
Standard
175 psi
VGF21ES40
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
150
Pressure Balanced
175 psi
Linear
VGF21LP40
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
155
Standard
175 psi
Linear
VGF21LS40
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
150
400 psi
250
Equal %
VGF22ES40
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
5"
250
250 psi
125
15 psi (2-position)
V5011A1882
V*-NO
V*-NO
V*-NO
V**-NO
V**-NO
V**-NO
250
250 psi
15 psi (2-position)
Stem up to close
V5011B1047
W*-NO W*-NO W*-NO W**-NO
W**-NO
W**-NO
285
Pressure Balanced
175 psi
125 psig / 353 F 
Stem down to close
VGF21EP50
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
285
Standard
175 psi
VGF21ES50
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
320
Pressure Balanced
175 psi
Linear
VGF21LP50
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
320
Standard
175 psi
Linear
VGF21LS50
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
320
400 psi
250
Equal %
VGF22ES50
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
6"
360
250 psi
125
15 psi (2-position)
V5011A1916
V*-NO
V*-NO
V*-NO
V**-NO
V**-NO
V**-NO
360
250 psi
15 psi (2-position)
Stem up to close
V5011B1070
W*-NO W*-NO W*-NO W**-NO
W**-NO
W**-NO
365
Pressure Balanced
175 psi
125 psig / 353 F 
Stem down to close
VGF21EP60
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
365
Standard
175 psi
VGF21ES60
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
370
Pressure Balanced
175 psi
Linear
VGF21LP60
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
370
Standard
175 psi
Linear
VGF21LS60
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
370
Standard
400 psi
250
Equal %
VGF22ES60
O*-NO O*-NO O*-NO
O**-NO
O**-NO
O**-NO
3-W
ay W
ater V
alves
4"
160
Mixing
250 psi
125
N/A
Constant Total
Stem up closes A-AB
V5013B1029
T-NC
T-NC
T-NC
T-NC
T-NC
T-NC
160
Diverting
250 psi
Constant Total
Stem up closes B-AB
V5013C1027
T-NC
T-NC
T-NC
T-NC
T-NC
T-NC
150
Mixing
175 psi
Equal % A-AB
Stem up closes A-AB
VGF31EM40
O-NC
O-NC
O-NC
O-NC
O-NC
O-NC
160
Diverting
175 psi
Linear, Constant Total Stem up closes B-AB
VGF31LD40
O-NC
O-NC
O-NC
O-NC
O-NC
O-NC
170
Mixing
400 psi
250
Equal % A-AB
Stem up closes A-AB
VGF32EM40
O-NC
O-NC
O-NC
O-NC
O-NC
O-NC
160
Diverting
400 psi
250
Linear, Constant Total Stem up closes B-AB
VGF32LD40
O-NC
O-NC
O-NC
O-NC
O-NC
O-NC
5"
250
Mixing
250 psi
125
Constant Total
Stem up closes A-AB
V5013B1037
T-NC
T-NC
T-NC
T-NC
T-NC
T-NC
250
Diverting
250 psi
Constant Total
Stem up closes B-AB
V5013C1035
T-NC
T-NC
T-NC
T-NC
T-NC
T-NC
320
Mixing
175 psi
Equal % A-AB
Stem up closes A-AB
VGF31EM50
O-NC
O-NC
O-NC
O-NC
O-NC
O-NC
285
Diverting
175 psi
Linear, Constant Total Stem up closes B-AB
VGF31LD50
O-NC
O-NC
O-NC
O-NC
O-NC
O-NC
320
Mixing
400 psi
250
Equal % A-AB
Stem up closes A-AB
VGF32EM50
O-NC
O-NC
O-NC
O-NC
O-NC
O-NC
285
Diverting
400 psi
250
Linear, Constant Total Stem up closes B-AB
VGF32LD50
O-NC
O-NC
O-NC
O-NC
O-NC
O-NC
6"
360
Mixing
250 psi
125
Constant Total
Stem up closes A-AB
V5013B1045
T-NC
T-NC
T-NC
T-NC
T-NC
T-NC
360
Diverting
250 psi
Constant Total
Stem up closes B-AB
V5013C1043
T-NC
T-NC
T-NC
T-NC
T-NC
T-NC
370
Mixing
175 psi
Equal % A-AB
Stem up closes A-AB
VGF31EM60
O-NC
O-NC
O-NC
O-NC
O-NC
O-NC
380
Diverting
175 psi
Linear, Constant Total Stem up closes B-AB
VGF31LD60
O-NC
O-NC
O-NC
O-NC
O-NC
O-NC
370
Mixing
400 psi
250
Equal % A-AB
Stem up closes A-AB
VGF32EM60
O-NC
O-NC
O-NC
O-NC
O-NC
O-NC
380
Diverting
400 psi
250
Linear, Constant Total Stem up closes B-AB
VGF32LD60
O-NC
O-NC
O-NC
O-NC
O-NC
O-NC
 
*The close-off pressure not to exceed rated pressure of steam valve
 
**The close-off pressure not to exceed rated pressure of steam valve. Use 4-11 spring range for positive positioner models.
 
NC = Normally Closed
 
NO = Normally Open
Flanged Globe Valves 4"- 6"
With Pneumatic Actuators
Common Features
•  Rolling diaphragm for long life and low hysteresis
•  Easily installation and attachment to the valve
•  Direct or reverse acting