Honeywell MS4103 ユーザーズマニュアル

ページ / 268
88
ML6161; ML7161
Used to control dampers in 
applications such as variable air 
volume (VAV) terminal units and for 
mounting on ball valves; suitable for 
use with SPDT or floating 
thermostats or building automation 
controls.
SPECIFICATIONS
Actuator Type ....................................... Damper
Rotational Stroke  .................................. 90 degrees
Fail Safe Mode  ..................................... Non-Spring Return
Rated Torque ........................................ 35 lb-in. (4 Nm) 
External Auxiliary Switches Available  .. Yes, 201052B
Electrical Connections  ......................... Screw terminals
Environmental Rating  ........................... NEMA1
Feedback  ............................................. With accessory
Frequency  ............................................ 50 Hz, 60 Hz
Manual operation  ................................. Declutch mechanism
Mounting  .............................................. Direct Coupled
Maximum Noise Rating, 
Driving (dBA @ 1m) .............................. 45
Timing, Nominal Driving at 60 Hz  ........ 90 sec., 180 sec. or 420 sec.
Power Consumption, Driving  ............... 1.8 VA or 5.4 VA
Rotation to Open  .................................. By wiring
Rotational Stroke Adjustment ............... Mechanically limited at 45 or 
60 degrees in cw or ccw 
directions
Compatible Damper Shafts .................. 3/8 to 1/2 in. square or round
 (10 to 13 square/round) 
Shaft Adapter Type  .............................. Aluminum Hub, two set screws
Supply Voltage  ..................................... 24 Vac ±20%
Materials ............................................... Steel plate and Plenum rated 
plastic
Operating Humidity Range (% RH) ...... 5 to 95% RH, non-condensing
Ambient Temperature Range  ............... 20 F to 125 F (-18 C to 50 C) 
Storage Temperature Range ................ 20 F to 130 F (-18 C to 54 C) 
Weight  .................................................. 1.5 lb (0.68 kg) 
Includes  ............................................... 4074ENY Bag Assembly
APPROVALS
CE  ........................................................ 89/336/ECC, 73/23/EEC
C-Tick ................................................... N314
Underwriters Laboratories, Inc.  ........... UL873, Plenum Rated
Canadian Underwriters 
Laboratories, Inc.  ................................. cUL C22.2 No. 24-93
FEATURES
• Control for air damper applications with up to 10 sq.ft. 
assuming 3.5 lb-in. per sq.ft. of damper area, velocity 
independent. 
• Superior A/C synchronous sub-motor for consistent timing 
and actuator longevity. 
• Eliminate need for limit switches or mechanical stops by 
providing magnetic coupling. 
• All models include manual declutch lever, and bag 
assembly with two minimum position setscrews. 
• Mount directly on 3/8 in. or 1/2 in. square or round damper 
shaft. 
• Selectable 45, 60, and 90 degree stroke in either clockwise 
or counterclockwise direction.
DIMENSIONS DIAGRAMS
1
(25)
M22990
OPTIONAL
AUXILIARY
SWITCH
T1
T2
-
+
+
24 Vac
2-10 Vdc
4-20 mA
4-7/8
(123)
4-1/4
(108)
5-9/16
(141)
11/16
(18)
1/8
(3)
5/16 (8)
1-11/16
(43)
3-3/8 (86)
1/8
(3)
15/32 (12)
1-5/16
(33)
3 (76)
2-7/8 (73)
1-11/16
(42)
1/8
(3)
1 (25)
M18016
CW
COM
CCW
OPTIONAL
AUXILIARY
SWITCH
11/16
(18)
3-3/8 (86)
4-1/4
(108)
4-7/8
(123)
2-7/8  (73)
1-11/16
(42)
1/8
(3)
1-5/16
(33)
7/8
(22)
2-1/2  (64)
M18018
5-7/8
(149)
1-13/16
(46)
1
(25)
3-5/8  (92)
1-13/16  (46)
3 IN. (76 MM)
MINIMUM SPACING
REQUIRED 
FOR REMOVING 
CONDUIT COVER
3-3/4  (95)
7/8
(22)
Non-Spring Return Direct Coupled Actuator
ml6161; ml7161