Honeywell MS4103 ユーザーズマニュアル

ページ / 268
95
Fire And Smoke Actuator
mS4209F; mS4309F; mS4709F; mS4809F; mS8209F; mS8309F
S
ubmitt
al Sheet
S
MS4209F; MS4309F; MS4709F; MS4809F; MS8209F; MS8309F
Spring return direct coupled 
actuators (DCA) for on/off damper 
control with an integral junction box. 
The actuator accepts an on/off signal 
from a single-pole, single-throw 
(SPST) controller. They are designed 
to operate reliably in smoke control 
systems requiring Underwriter's 
Laboratories Inc. UL555S ratings up 
to 350 F.
SPECIFICATIONS
Actuator Type  ....................................... Damper
Rotational Stroke  .................................. 95 ±3 degrees
Fail Safe Mode  ..................................... Spring Return
Rated Torque ........................................ 80 lb-in. (9 Nm) 
Maximum Stall Torque  .......................... 240 lb-in. (27 Nm)
Minimum Driving Torque at 350 F  ........ 80 lb-in. (9 Nm) 
Spring Return Torque  ........................... 80 lb-in. (9 Nm) 
External Auxiliary Switches Available  .. Yes, 32003532-005
Electrical Connections  ......................... Two color-coded leads
Electrical Connection Length ............... 16 in. (406 mm)
Environmental Rating  ........................... NEMA1
Frequency  ............................................ 60 Hz
Mounting  .............................................. Direct Coupled
Maximum Noise Rating, 
Holding (dBA @ 1m)  ............................ 20 (no audible noise)
Maximum Noise Rating, 
Driving (dBA @ 1m) .............................. 80
Compatible Damper Shafts ..................  3/8 to 1/2 in. square or round 
(10 to 13 square/round)
Shaft Adapter Type  .............................. Aluminum Hub, four set screws
Supply Voltage  ..................................... 120 Vac +10%, -15%
Materials ............................................... Aluminum housing
Operating Humidity Range (% RH) ...... 5 to 95% RH, non-condensing
Ambient Temperature Range  ............... 0 F to 130 F (-18 C to 55 C)
Storage Temperature Range  ................ -40 F to 140 F (-40 C to 60 C)
Weight  ..................................................  6 lb (2.72 kg)
Comments ............................................ Integral junction box with three 
7/8 in. conduit openings 
(fittings not included)
APPROVALS
CE ......................................................... 89/336/ECC, 73/23/EEC
C-Tick ................................................... N314
Underwriters Laboratories, Inc. ............ UL873, Plenum Rated
Canadian Underwriters Laboratories, Inc. cUL C22.2 No. 24-93
FEATURES
• Integral spring return ensures level of return torque. 
• Fifteen-second spring return timing. 
• No special cycling required during long-term holding. 
• No audible noise during holding. 
• Patent pending design eliminates need for limit switches to 
reduce power consumption. 
• Models available for 24, 120, and 230 Vac. 
• Ninety-five degree angle of rotation for tight damper 
closure. 
• Actuator holds rated torque at reduced power level. 
• Die-cast aluminum housing. Housing design allows flush 
mounting to damper. 
• Integral junction box with three conduit openings eliminates 
need for separate wiring box. 
• High-temperature indicator included.
DIMENSIONS DIAGRAM
2 (51)
1 (25)
5/8 
(17)
6 3/8
(161)
7 1/2 
(192)
4 (102)
7/8 (22)
5 1/8 (129)
2 (51)
3 5/16 (84)
1/16 (2)
M17508