4   INSTALLATION, WIRING AND MAINTENANCE OF THE PRODUCT
[Wiring examples using duct (incorrect example and corrected example)]
Relay
Drive 
unit
Drive 
unit
Noise source
Relay
Relay
PLC
QD
75
Relay
Relay
Relay
PLC
QD
75
Drive 
unit
Drive 
unit
Changed
Wiring duct
Wiring duct
Control panel
Control panel
The QD75 and drive units are 
placed closely. The connection 
cable between the QD75 and 
drive units is separately laid 
from the power line (in this 
example, the cable is outside of 
the duct) and is as short as possible.
(power system, 
etc.)
Noise source
(power system, 
etc.)
The drive units are placed 
near the noise source. 
The connection cable between 
the QD75 and drive units is 
too long.
(11) The influence of noise may be reduced by installing ferrite cores to the cable
connected to the QD75 as a noise reduction technique.
For the noise reduction techniques related to connection with the servo amplifier,
also refer to the instruction manual of the servo amplifier.
(12) If compliance with the EMC directive is not required, the influence of external
noise may be reduced by making the configuration compliant with the EMC
directive.
For the configuration compliant with the EMC directive, refer to Chapter 3 "EMC
AND LOW-VOLTAGE DIRECTIVES" in the User's Manual (Hardware) of the
used CPU module.