Mitsubishi Electronics QD75P4N ユーザーズマニュアル
11 - 10
MELSEC-Q
11 MANUAL CONTROL
11.2.4 Creating start programs for JOG operation
A sequence program must be created to execute a JOG operation. Consider the
"required control data setting", "start conditions" and "start time chart" when creating
the program.
The following shows an example when a JOG operation is started for axis 1.
(" Cd.17 JOG speed" is set to "100.00mm/min" in the example shown.)
"required control data setting", "start conditions" and "start time chart" when creating
the program.
The following shows an example when a JOG operation is started for axis 1.
(" Cd.17 JOG speed" is set to "100.00mm/min" in the example shown.)
Required control data setting
The control data shown below must be set to execute a JOG operation. The
setting is carried out with the sequence program.
setting is carried out with the sequence program.
Setting item
Setting
value
Setting details
Buffer memory address
Axis
1
Axis
2
Axis
3
Axis
4
Cd.16
Inching movement
amount
amount
0 Set
“0”.
1517
1617
1717 1817
Cd.17 JOG speed
10000
Set a value equal to or above the " Pr.7 Bias
speed at start" and equal to or below the
" Pr.31 JOG speed limit value".
speed at start" and equal to or below the
" Pr.31 JOG speed limit value".
1518
1519
1519
1618
1619
1619
1718
1719
1719
1818
1819
1819
Refer to Section 5.7 "List of control data" for details on the setting details.
Start conditions
The following conditions must be fulfilled when starting. The required conditions
must also be assembled in the sequence program, and the sequence program
must be configured so the operation will not start if the conditions are not fulfilled.
must also be assembled in the sequence program, and the sequence program
must be configured so the operation will not start if the conditions are not fulfilled.
Signal name
Signal state
Device
Axis
1
Axis
2
Axis
3
Axis
4
Interface
signal
signal
PLC READY signal
ON
CPU module preparation
completed
completed
Y0
QD75 READY signal
ON QD75 preparation completed
X0
Synchronization flag
ON
QD75 buffer memory
The access is possible.
The access is possible.
X1
Axis stop signal
OFF Axis stop signal is OFF
Y4 Y5 Y6
Y7
Start complete signal
OFF Start complete signal is OFF
X10 X11 X12 X13
BUSY signal
OFF QD75 is not operating
XC XD XE
XF
Error detection signal
OFF There is no error
X8 X9 XA
XB
M code ON signal
OFF M code ON signal is OFF
X4 X5 X6
X7
External
signal
signal
Drive unit READY signal ON Drive unit preparation completed
–
Stop signal
OFF Stop signal is OFF
–
Upper limit (FLS)
ON Within limit range
–
Lower limit (RLS)
ON Within limit range
–
If the CPU module is set to the asynchronous mode in the synchronization setting, this must be
inserted in the program for interlocking. If it is set to the synchronous mode, it must not be
inserted in the program for interlocking because it is turned ON when the CPU module executes
calculation.
inserted in the program for interlocking because it is turned ON when the CPU module executes
calculation.