Fig. 6. Alarm status messaging 
 
NOTE:
 
The active state and passive state are defined in the "Active State" 
datapoint attribute. 
 
 
 
Alarm Status (V2.04.xx or higher) 
 
Alarm monitoring 
In the case of a digital input or a pseudo digital point, the attribute "Alarm Status" 
specifies whether or not alarm monitoring is required. 
The following entries are possible: 
 
•  Yes:  Alarm monitoring is required 
•  No: 
Alarm monitoring is not required 
 
When alarm monitoring is required, the alarm message occurs depending on the 
physical contact status and on the logical status as defined in the online attribute 
“Normally Open/Normally Closed”. 
 
 
Alarm Type 
The attributes listed in Table 5 are capable not only of generating alarms, but also 
of writing them to the internal alarm memory and sending them to the PC front-end 
or to the modem module (when connected). 
 
Table 5. Alarm attributes 
 
attribute 
always critical 
optional critical or non-critical 
Operating Mode 
 
Min. Limit 
 
Max. Limit 
 
Maintenance 
Alarm 
 
Interval Counter 
 
Alarm Status 
 
 
Changing over the attribute "Operating Mode" always results in a critical alarm, but 
the attribute "Alarm Type" offers a choice for the alarm attributes "Min. Limit", "Max. 
Limit", "Maintenance Alarm", "Totalizer", and "Alarm Status" whether an alarm is 
classified as critical or non-critical. Distinguishing between critical and non-critical 
alarms is significant for the subsequent reporting of the alarms to the PC front-end 
or to the modem module. Compared to non-critical alarms, critical alarms are given 
priority on the bus when several alarms are in the alarm queue. When the type of 
alarm for a datapoint has been decided, e.g. "critical" alarm type, it refers to all 
alarm attributes for this datapoint. 
 
 
 
 
 
Alarm Definition 
DI in  
“Active State” 
DI in  
“Passive State”