Honeywell R0512 ユーザーズマニュアル

ページ / 86
ATTRIBUTES 
EXCEL 50/100/500/600/800 
EN2B-0092GE51 R0512 
24 
 
 
PT 1000/2 
Hysteresis increases approx. linearly with temperature. 
Average hysteresis: 
1.6 K (2.9 °F) 
Hyst. At 0 °C (32 °F): 
1.3 K (2.3 °F) 
Hyst. At 400 °C (752 °F): 
2.0 K (3.6 °F) 
 
 
PT 3000 (not with Excel 100C) 
Hysteresis increases approx. linearly with temperature. 
Average hysteresis: 
0.8 K (1.4 °F) 
Hyst. At -45 °C (-49 °F): 
0.7 K (1.3 °F) 
Hyst. At 145 °C (293 °F): 
1.0 K (1.8 °F) 
 
 
Balco 500 (not with Excel 100C) 
Hysteresis decreases approx. linearly with temperature. 
Average hysteresis: 
0.9 K (1.6 °F) 
Hyst. At -50 °C (-49 °F): 
1.0 K (1.8 °F) 
Hyst. At 150 °C (293 °F): 
0.7 K (1.3 °F) 
 
 
Input/Output Status Text (prior to V2.04.xx) 
 2 status texts per digital data output 
Two status texts can be assigned to each digital datapoint status. Status texts give 
an overview of the condition of the sensor or switching device connected to the 
datapoint. 
 
The associated status text appears in the attribute "Value" depending on the actual 
point status. 
 
For instance, the status texts could be as follows for a point connected to a digital 
output: 
 
Digital point status 0:  
Status Text: 
"Passive” 
Digital point status 1: 
Status Text: 
"Active” 
 
 
Table 9. Relationships between I/O Status, Active State, and Status Text 
 
Input/Output Status 
Active State (prior to V.2.04.x) 
Status Text 
active 
passive 
passive 
active 
 
  Status Text with flexible datapoints 
The attribute "Status Text" allows you to describe the value sent to the controller by 
the digital output Pulse 1 and by flexible datapoints. In the case of flexible 
datapoints of the type "feedback", the status text refers to the value of the feedback 
flexible datapoint and not to the required value. 
 
 
Input/Output Status Text (V2.04.xx or higher) 
With firmware 2.04.xx or higher, the relationship between physical output status and 
logical output status as defined by the attribute "Normally Open/Normally Closed" 
determines the display of the equivalent status text. See section "Normally 
Open/Normally Closed (V2.04.xx or higher)" on page 28 
for details. 
 
 
Interval Count 
 
Interval count 
The  attribute "Interval Count" shows the totalizer value (pulse x scaling factor) 
accumulated since the last reset. 
 
 
Displaying the interval count 
The attribute "Interval Count" can be viewed on the XI581, XI582, and Excel 50 MMI 
operating units as well as via the XL-Online Operating Software and building 
Supervisor front-ends like XBS, EBI and XFI. Based on mathematical rounding, it is