(3) Low speed detection (LS signal, Pr. 865)
⋅ The low speed detection signal (LS) is output when the
output frequency drops below the Pr. 865  Low speed
detection
 setting.
⋅ When speed control is performed by Real sensorless
vector control or vector control, a fault (E.OLT) is
displayed and the inverter trips if frequency drops to the
Pr. 865 setting by torque limit operation and the output
torque exceeds Pr. 874 OLT level setting and remains for
more than 3s.
⋅ For the LS signal, set "34 (positive logic) or 134 (negative
logic)" in Pr. 190 to Pr. 196 (output terminal function
selection)
 and assign functions to the output terminal. 
REMARKS
The FU signal is assigned to the terminal FU and the SU signal is assigned to the terminal SU in the initial setting.
All signals are OFF during DC injection brake, pre-excitation (zero speed control, servo lock), or start time tuning.
⋅ The type of frequency (output as the following signals), which is compared with the set frequency, differs by the
control method. 
 
CAUTION
⋅ When terminal assignment is changed using Pr. 190 to Pr. 196 (output terminal function selection), the other functions may be
affected. Set parameters after confirming the function of each terminal.
♦ Parameters referred to 
Pr. 190 to Pr. 196 (output terminal function selection)   
 Refer to page 239
Pr. 874 OLT level setting   
 Refer to page 100
ON
LS
ON
OFF
Pr.865
Output frequency 
(Hz)
Time
Control Method
Compared frequency
FU, FU2, FU3
FB, FB2, FB3, SU, LS
V/F control
Output frequency
Output frequency
Advanced magnetic 
flux vector control
Output frequency before the slip compensation. 
Output frequency before the slip compensation. 
Real sensorless 
vector control
Frequency command
Estimated frequency (estimated from the actual 
motor speed)
Encoder feedback 
control
Actual motor speed converted as frequency
Actual motor speed converted as frequency
Vector control
Frequency command
Actual motor speed converted as frequency