Mitsubishi Electronics FR-A700 ユーザーズマニュアル

ページ / 523
268
Operation selection at power failure 
and instantaneous power failure
Without frequency search
When  Pr. 162  = "1" or "11", automatic restart operation is
performed in a reduced voltage system, where the voltage is
gradually risen with the output frequency unchanged from prior
to an instantaneous power failure independently of the
coasting speed of the motor.
For Real sensorless vector control, output frequency and
voltage before instantaneous power failure are output. (Pr. 58 is
invalid.)
Encoder detection frequency search
⋅ When "2 or 12" is set in Pr. 162 under encoder feedback
control, the motor starts at the motor speed and in the rotation
direction detected from the encoder at power restoration.
⋅ Encoder detection frequency search is performed regardless
of the Pr. 162 setting under vector control.
⋅ The Pr. 58 and Pr. 299 settings are invalid for encoder detection
frequency search.
Restart operation at every start
When  Pr. 162 = "10, 11 or 12", automatic restart operation is
also performed every start, in addition to the automatic restart
after instantaneous power failure. When Pr. 162 = "0, 1 or 2",
automatic restart operation is performed at the first start after
power supply-on, but the inverter starts at the starting
frequency at the second time or later.
When Pr. 162 = 1, 11 (without frequency search)
V/F control, Advanced magnetic flux vector control
Real sensorless vector control
Coasting time
Pr.57 setting
*
Instantaneous (power failure) time
Power supply
(R/L1, S/L2, 
T/L3)
Motor speed N 
(r/min)
Inverter output 
frequency f(Hz)
Inverter output 
voltage E(V)
Restart cushion time
(Pr.58 setting)
*  The output shut off timing differs 
according to the load condition.
Coasting time
Pr.57 setting
*
Instantaneous (power failure) time
Power supply
(R/L1, S/L2, 
T/L3)
Motor speed N 
(r/min)
Inverter output 
frequency f(Hz)
output voltage 
E(V)
*  The output shut off timing differs 
according to the load condition.
REMARKS
⋅ This system stores the output frequency prior to an
instantaneous power failure and increases the voltage.
Therefore, if the instantaneous power failure time exceeds 0.2s,
the inverter starts at Pr. 13 Starting frequency (initial value = 0.5Hz)
since the stored output frequency cannot be retained.
Instantaneous 
(power failure) time
Power supply
(R/L1, S/L2, T/L3)
Motor speed N
(r/min)
Inverter output 
frequency f(Hz)
Output voltage E(V)
Coasting time
(Pr.57)
* The output shut off timing differs according to the load condition.
*
Acceleration time 
at a restart 
(Pr.611 setting)
When  Pr. 162 = 2, 12 (encoder detection
frequency search)
REMARKS
⋅ When encoder feedback control is invalid, setting "2 or 12" in Pr.
162 enables frequency search (Pr. 162 = "0, 10").