Mitsubishi Electronics FR-A700 ユーザーズマニュアル

ページ / 523
304
c) Method to adjust torque only without adjustment of gain voltage (current)
(when changing gain torque from 150% to 130%) 
REMARKS
· For operation from the parameter unit (FR-PU04/FR-PU07), refer to the instruction manual of the FR-PU04/FR-PU07.
· Set bias torque setting using calibration parameter C16 (Pr. 919) or C38 (Pr. 932).  (Refer to page 301)
CAUTION
Be cautious when setting any value other than "0" as the bias torque at 0V (0mA). Torque is applied to the motor 
by merely tuning ON the start signal without torque command.
♦ Parameters referred to 
Pr. 20 Acceleration/deceleration reference frequency 
 Refer to page 172
Pr. 73 Analog input selection, Pr. 267 Terminal 4 input selection 
 Refer to page 286
Pr. 79 Operation mode selection 
 Refer to page 313
Pr. 858 Terminal 4 function assignment, Pr. 868 Terminal 1 function assignment 
 Refer to page 285
Flicker...Parameter setting complete!!
Display
Operation
1. 
Pr.920) or 
(Pr.933) appears.
3. 
Turn
o change the set value to 
       "           " (130.0%)
4. 
Press        to set.
5. 
Mode/monitor check 
Press        twice to choose the 
monitor/frequency monitor.
6. 
Apply a voltage across the inverter 
terminals 1 and 5 (across 4 and 5) and 
turn on the start command (STF, STR). 
Operation starts with 130% torque.
2. 
Press        to show the present set value. 
(150%)
or
Terminal 1 input
Terminal 4 input
Terminal 1 input Terminal 4 input