Mitsubishi Electronics FR-A700 ユーザーズマニュアル

ページ / 523
371
4
⋅ The input signals are as indicated below.
⋅ The output signals are as indicated below.
Signal Terminal Used
Function
Operation
MC Operation 
 
*6
MC1
 
*5
MC2
MC3
MRS
MRS
Operation enable/disable 
selection
 
*1
ON ..... Bypass-inverter operation 
enabled
OFF ... Bypass-inverter operation 
disabled
×
No 
change
CS
CS
Inverter/bypass 
*2
ON...... Inverter operation
×
OFF ... Bypass operation
×
STF
(STR)
STF(STR)
Inverter operation command 
(Invalid for bypass)
 
*3
ON...... Forward rotation (reverse 
rotation)
×
OFF.... Stop
×
OH
Set "7" in any of 
Pr. 180 to Pr. 189.
External thermal relay input
ON ..... Motor normal
OFF.... Motor abnormal
×
×
×
RES
RES
Operating status initialization 
*4
ON...... Initialization
No 
change
×
No 
change
OFF.... Normal operation
*1
Unless the MRS signal is turned ON, neither bypass operation nor inverter operation can be performed.
*2
The CS signal functions only when the MRS signal is ON.
*3
STF (STR) functions only when both the MRS signal and CS signal are ON.
*4
The RES signal enables reset input acceptance selection using Pr. 75 Reset selection/disconnected PU detection/PU stop selection.
*5
MC1 turns OFF when an inverter fault occurs.
*6
MC operation
: MC-ON
×
: MC-OFF
: Inverter operation ................ MC2 is OFF and MC3 is ON
Bypass operation ................ MC2 is ON and MC3 is OFF
No change  : The status before the signal turns ON or OFF is held.
Signal
Terminal Used
(Pr. 190 to Pr. 196  setting)
Description
MC1
17
Control signal output of inverter input side magnetic 
contactor MC1
MC2
18
Control signal output of bypass operation magnetic 
contactor MC2
MC3
19
Control signal output of inverter output side 
magnetic contactor MC3