Mitsubishi Electronics FR-A700 ユーザーズマニュアル

ページ / 523
11/24
BCN-C22005-634
(4) Utilizing or changing offline auto tuning data
The data measured in the offline auto tuning can be read and utilized or changed.
<Operating procedure>
1)Set Pr. 71 according to the motor used.
2) In the parameter setting mode, read the following parameters and set desired values.
The display units of the read motor constants can be changed with Pr. 684 Tuning data unit switchover
Setting Pr.684 = "1" does not change the parameter settings.
If the current fluctuates after tuning, adjust the constant by referring to the induced voltage constant, which can
be found in the data sheet.
Motor
Pr. 71 Setting
IPM motor
MM-CF
334
Other than MM-CF
8094
Parameter
Number
Name
Setting Increments
Read Value
Setting 
Range
Pr.684 = 0
Pr.684 = 1
Pr.71 = 334
Pr.71 = 8094
90
Motor constant (R1)
Internal data
0.001
/
0.01m
 
Tuned data 
Tuned data 
0 to ***
9999
92
Motor constant (L1)/d-
shaft inductance
Internal data
0.1mH/
0.01mH 
9999 
Tuned data 
0 to ***
9999
93
Motor constant (L2)/q-
shaft inductance
Internal data
0.1mH/
0.01mH 
9999 
Tuned data 
0 to ***
9999
711
Motor d-shaft 
inductance Ld decay 
ratio
Internal data
0.1%
9999 
Tuned data 
0 to ***
9999
712
Motor q-shaft 
inductance Lq decay 
ratio
Internal data
0.1%
9999 
Tuned data 
0 to ***
9999
721
Starting magnetic pole 
position detection 
pulse width
Internal data
1(
s)
9999 
Tuned data 
0 to ***
9999
859
Torque current
Internal data
0.01A/0.1A 
Tuned data 
Tuned data 
0 to ***
9999
*1
As the motor constants measured in the offline auto tuning have been converted into internal data (****), refer to the following setting
example when making setting:
Setting example To slightly increase Pr. 90 value (5%) 
When Pr. 90 is displayed "2516", 
set 2642, i.e. 2516 
 1.05 = 2641.8, in Pr. 90 .
(The value displayed has been converted into a value for internal use. Hence, simple addition of a given value to the
displayed value has no significance.)
*2
Setting "9999" selects the IPM motor (MM-CF) constant.
*3
Initial values differ according to the inverter capacity. (55K or lower/75K or higher)
Parameter
Number
Name
Setting Range
Setting Increments
Initial Setting
706
Induced voltage constant
0 to 5000
9999
0.1(mV/(rad/s))
9999 
*
* Setting "9999" sets a calculated value based on tuning.
bcnc22005634.fm  11 ページ  2012年7月3日 火曜日 午前9時43分