Hitachi L200 ユーザーズマニュアル

ページ / 280
“A” Group: Standard Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–28
Additional Analog Input Settings
Input Range Settings – The parameters in the following table adjust the input charac-
teristics of the analog current input. When using the inputs to command the inverter 
output frequency, these parameters adjust the starting and ending ranges for the current, 
as well as the output frequency range. Related characteristic diagrams are located in 
.
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
A101 [OI]–[L] input active 
range start frequency
The output frequency corre-
sponding to the current input 
range starting point.
Range is 0.00 to 400.0 Hz
0.0
0.0
Hz
OI-EXS  0000.0Hz
A102 [OI]–[L] input active 
range end frequency
The output frequency corre-
sponding to the current input 
range ending point.
Range is 0.00 to 400.0 Hz
0.0
0.0
Hz
OI-EXE  0000.0Hz
A103 [OI]–[L] input active 
range start current
The starting point for the 
current input range.
Range is 0. to 100.%
0.0
0.0
%
OI-EX%S   00000%
A104 [OI]–[L] input active 
range end current
The ending point for the 
current input range.
Range is 0. to 100.%
100.
100.
%
OI-EX%E   00100%
A105 [OI]–[L] input start 
frequency enable
Two options:
00... Use A101 start value
01... Use 0Hz
01
01
OI-LVL    0Hz