Hitachi L200 ユーザーズマニュアル

ページ / 280
L200 Inverter
Appendix B
B–15
Write in Coils [0Fh]:
This function writes data in consecutive coils. An example follows:
• Change the state of intelligent input terminal [1] to [5] of an inverter having a slave 
address “5.”
• This example assumes the intelligent input terminals have terminal states listed below.
Item
Data
Intelligent input terminal
[1]
[2]
[3]
[4]
[5]
Coil number
7
8
9
10
11
Terminal status
ON
ON
ON
OFF
ON
Query:
Note 1:
Broadcasting is disabled.
Note 2:
The change data is a set of 
high-order data and low-order 
data. So when the size (in 
bytes) of data to be changed is 
an odd number, add “1” to the 
data size (in bytes) to make it 
an even number.
Response:
No.
Field Name
Example
(Hex)
1
Slave address *1
05
2
Function code
0F
3
Coil start number 
(high order)
00
4
Coil start number 
(low order)
07
5
Number of coils 
(high order)
00
6
Number of coils (low 
order)
06
7
Byte number *2
02
8
Change data
(high order) *2
17
9
Change data
(low order) *2
00
10
CRC-16 (high order)
DA
11
CRC-16 (low order)
EF
No.
Field Name
Example
(Hex)
1
Slave address
05
2
Function code
0F
3
Data size (in bytes)
00
4
Coil data *3
07
5
Number of coils 
(high order)
00
6
Number of coils 
(low order)
06
7
CRC-16 (high order)
65
8
CRC-16 (low order)
8C