Mitsubishi Electronics FR-A500 ユーザーズマニュアル

ページ / 257
109
4
How to make a restart after a stop made by the           key from the PU during
external operation
(1) Operation panel (FR-DU04)
1) After completion of deceleration to a stop, switch off the STF or STR signal.
2)Press the 
 key three times* to call the 
 indication. (Note 8)
(*: For monitor screen)  .... Refer to page 53 for the monitor display provided by pressing the 
 key.
3) Press the 
 key.
4) Turn on the STF or STR signal.
(2) Parameter unit (FR-PU04)
1) After completion of deceleration to a stop, switch off the STF or STR signal.
2) Press the 
 key.
3) Switch on the STF or STR signal.
The other way of making a restart other than the above method is to perform a power-reset or to make a
reset with the inverter reset terminal.
Note: When Pr. 79 = "3", press the 
 key three times to display 
, then press the 
 key and
proceed to step 3).
Note: 1. By entering the reset signal (RES) during operation, the inverter shuts off output while it is reset,
the data of the electronic overcurrent protection and regenerative brake duty are reset, and the
motor coasts.
2. The PU disconnection detection function judges that the PU connector is disconnected when it is
removed from the inverter for more than 1s. If the PU had been disconnected before power-on, it
is not judged as an alarm.
3. To resume operation, reset the inverter after confirming that the PU is connected securely.
4. When PU disconnection detection is set and the PU is then disconnected during PU jog
operation, the motor decelerates to a stop. The motor will not stop if a PU disconnection alarm
occurs.
5. The Pr. 75 value can be set any time. Also, if parameter (all) clear is executed, this setting will not
return to the initial value.
6. When the motor is stopped by the PU stop function, PS is displayed but an alarm is not output.
When the PU connector is used for RS-485 communication operation, the reset selection and PU
stop selection functions are valid but the PU disconnection detection function is invalid.
7. The reset key of the PU is only valid when the protective function is activated, independent of the
Pr. 75 setting.
 CAUTION
Do not reset the inverter with the start signal on.
Otherwise, the motor will start instantly after resetting, which may lead to hazardous 
conditions.
STOP
RESET
MODE
MODE
MODE
EXT
EXT
STF     ON
(STR)   OFF
S
peed
peration panel
Time
Stop and restart example for external operation
 key
SET
 key
STOP
RESET