Mitsubishi Electronics FR-A500 ユーザーズマニュアル

ページ / 257
203
5
(2) Minor fault
When the protective function is activated, the output is not shut off. You can make parameter setting to 
output the minor fault signal. (Set "98" in any of Pr. 190 to Pr. 195 (output terminal function selection). Refer 
to page 162)
(3) Warnings
Note: 5. The stall prevention operation current may be set as desired. It is factory-set to 150%.
Operation Panel  
Indication
E.ECT
FR-PU04
No encoder signal
Name
Wire break detection
Description
The inverter output is stopped if the encoder signal is turned off during orientation, 
encoder feedback or vector control executed with the FR-A5AP.
Check point
Check for encoder signal wire break.
Corrective action
Repair wire break.
Operation Panel  
Indication
FN
FR-PU04
Fan fault
Name
Fan fault
Description
For the inverter, which contains a cooling fan, FN appears on the operation panel 
when the cooling fan stops due to a fault or operates differently from the setting of 
Pr. 244 "cooling fan operation selection".
Check point
Check the cooling fan for a fault.
Corrective action
Replace the fan.
Operation Panel  
Indication
OL
FR-PU04
OL
Name
Stall prevention (Over current)
Description
During 
acceleration
If a current of more than 150% (Note 5) of the rated inverter 
current flows in the motor, this function stops the increase in 
frequency until the overload current reduces to prevent the 
inverter from resulting in overcurrent shut-off. When the 
overload current has reduced below 150%, this function 
increases the frequency again.
During constant-
speed operation
If a current of more than 150% (Note 5) of the rated inverter 
current flows in the motor, this function lowers the frequency 
until the overload current reduces to prevent overcurrent shut-
off. When the overload current has reduced below 150%, this 
function increases the frequency up to the set value.
During 
deceleration
If a current of more than 150% (Note 5) of the rated inverter 
current flows in the motor, this function stops the decrease in 
frequency until the overload current reduces to prevent the 
inverter from resulting in overcurrent shut-off. When the 
overload current has reduced below 150%, this function 
decreases the frequency again.
Check point
Check the motor for use under overload.
Corrective action
The acceleration time may change. Increase the stall prevention operation level 
using Pr. 22 "stall prevention operation level" or make the stall prevention 
inoperative using Pr. 156 "stall prevention operation selection".