Mitsubishi Electronics FR-A500 ユーザーズマニュアル

ページ / 257
65
Pal
a
me
te
r Lis
t
4
Se
c
o
nd f
unc
ti
ons
44
Second acceleration/deceleration 
time
0 to 3600 s/
0 to 360 s
0.1 s/0.01 s
5 s
45
Second deceleration time
0 to 3600 s/0 to 360 s, 
9999
0.1 s/0.01 s
9999
46
Second torque boost (Note 1)
0 to 30%, 9999
0.1%
9999
47
Second V/F (base frequency) (Note 
1)
0 to 400Hz, 9999
0.01Hz
9999
48
Second stall prevention operation 
current
0 to 200%
0.1%
150%
49
Second stall prevention operation 
frequency
0 to 400Hz, 9999
0.01Hz
0Hz
50
Second output frequency detection
0 to 400Hz
0.01Hz
30Hz
Dis
pla
y
 f
unc
ti
on
s
52
DU/PU main display data selection
0 to 20, 22, 23, 24, 25, 
100
1
0
53
PU level display data selection
0 to 3, 5 to 14, 17, 18
1
1
54
FM terminal function selection
1 to 3, 5 to 14,
17, 18, 21
1
1
55
Frequency monitoring reference
0 to 400Hz
0.01Hz
60Hz
56
Current monitoring reference
0 to 500A
0.01A
Rated output 
current
Au
to
m
a
ti
c
re
s
tart
fun
c
ti
o
n
s
57
Restart coasting time
0, 0.1 to 5 s, 9999
0.1 s
9999
58
Restart cushion time
0 to 60 s
0.1 s
1.0 s
Addi
tio
nal
fu
nc
ti
on
59
Remote setting function selection
0, 1, 2
1
0
O
per
ati
on s
e
lec
tion f
unc
ti
ons
60
Intelligent mode selection
0 to 8
1
0
61
Reference I for intelligent mode
0 to 500A, 9999
0.01A
9999
62
Ref. I for intelligent mode accel.
0 to 200%, 9999
0.1%
9999
63
Ref. I for intelligent mode decel.
0 to 200%, 9999
0.1%
9999
64
Starting frequency for elevator 
mode
0 to 10Hz, 9999
0.01Hz
9999
65
Retry selection
0 to 5
1
0
66
Stall prevention operation level 
reduction starting frequency
0 to 400Hz
0.01Hz
60Hz
67
Number of retries at alarm 
occurrence
0 to 10,101 to 110
1
0
68
Retry waiting time
0 to 10 s
0.1 s
1 s
69
Retry count display erasure
0

0
70
Special regenerative brake duty
0 to 15%/0 to 30%/0% 
(Note 10)
0.1%
0%
71
Applied motor
0 to 8, 13 to 18, 20, 23, 
24
1
0
72
PWM frequency selection
0 to 15
1
2
73
0-5V/0-10V selection
0 to 5, 10 to 15
1
1
74
Filter time constant
0 to 8
1
1
75
Reset selection/disconnected PU 
detection/PU stop selection
0 to 3, 14 to 17
1
14
76
Alarm code output selection
0, 1, 2, 3
1
0
77
Parameter write disable selection
0, 1, 2
1
0
78
Reverse rotation prevention 
selection
0, 1, 2
1
0
79
Operation mode selection
0 to 8
1
0
Func-
tion
Parameter 
Number
Name
Setting Range
Minimum 
Setting 
Increments
Factory Setting
Refer 
To
Page: