AEG 8000012364 BAL ユーザーズマニュアル

ページ / 42
"UniVert 2" inverter 
 
Page 21 of 42 
8000012364 BAL, en 
Function of the SBS (optional) 
For the technical data or unit settings, refer to the chapter “Technical 
Data”. 
4.1 Operating 
Statuses 
The following operating statuses are possible: 
 
"PowerUp": 
Status after PowerUp or Reset. The control system checks the 
ambient conditions. 
 
"on": 
Mains operation: The SBS supplies the load. 
 
"ready": 
In the event of load voltage deviation or INV failure / switch-off, the 
SBS takes over the load without interruption, i.e. the SBS control 
system switches over to the "on" operating status. 
 
"blocked": 
The SBS control unit is blocked. In the event of load voltage deviation 
or INV failure / switch-off, the SBS does not take over the load, i.e. 
the SBS control system remains in the "blocked" operating status. 
The operating status "blocked" is activated in the event of mains 
failures or phase deviations. 
 
"Fault": 
A fault has occurred in the SBS. This fault must be remedied and 
acknowledged using the Reset button. 
 
 
ATTENTION:  
If the INV is switched off in the event of a blocked or faulty SBS, the 
loads are no longer supplied with power.
 
 
4.2 Switchback 
Attempts 
Should the load voltage deviate excessively e.g. due to overload of 
the INVs or load short circuits (see chapter 4.4), the loads are 
automatically switched over to the SBS without interruption. Then the 
loads are also automatically switched back to the INV. It this 
switchback attempt fails, the SBS continues to supply the loads. After 
3 unsuccessful switchback attempts within 1 minute, the INV is 
switched off and the loads remain supplied by the SBS.