"UniVert 2" inverter 
 
Page 24 of 42 
8000012364 BAL, en 
Switches S3.7 and S3.8: number of redundant INVs 
 
S3.7 S3.8 
0 INVs 
0 0 
1 INV 
0 1 
2 INVs 
1 0 
3 INVs 
1 1 
 
The settings must be the same on all INVs and the SBS! 
Standard setting: S3.7 and S3.8 open 
 
Switches S3.4 and S3.5: not used 
 
Switch S3.6: Switchover with gap (yes/no) 
Standard setting: switchover
 not with gap - S3.6 open 
i.e. in the event of phase deviations between INV and SBS, the SBS 
blocks. 
 
If switchover with gap is selected (- S3.6 closed), the SBS does not 
block in the event of a phase deviation (see chapter 4.12). 
 
4.12 Signalling, 
Displays 
and Remote Signals (X4) 
The following signals are indicated via LEDs on the front panel: 
 
Display Colour 
Operating 
status 
SBS 
operation 
green 
SBS is in operation, 
operating voltage present 
INV present 
green 
INV voltage present 
Mains 
present 
green 
Mains voltage present 
Synchronism green 
Mains and INV run synchronously 
Load on INV  green 
The INV supplies the load 
Load 
on the mains 
green 
The mains supplies the load 
Collective 
fault 
red 
Collective fault signal delayed by 20 s, 
the signalling relay is triggered at the same 
time. 
 
The unit is equipped with a liquid-crystal display. 
The following displays are to be expected during the corresponding 
operating statuses. 
 
Mains operation: 
"U=230.0V" Load 
voltage 
"I=13.7A" SBS 
current