Operation with Advanced Microprocessor with Graphics Control
25
3.8.4 DIP Switches
The DIP switch settings can be reviewed from the display panel. Changing the DIP switches requires 
opening the front panel for access to the DIP switches on the microprocessor control board.
These selections should match options installed on your unit and should not need to change during 
normal operation. Switches 1 through 7 are self explanatory. DIP switch 8, not shown in Table 11
below, enables the password feature when set to ON and disables the password feature if set to OFF.
3.9
Date and Time
The current date and time is available through the display. This feature allows the date and time to 
be read or changed and is accessed by selecting “DATE AND TIME” from the Main Menu. The “DATE 
AND TIME” is used by the control for recording the Alarm History and plotting graphs. 
3.10 Plot Graphs
Selecting PLOT GRAPHS will step to the following menu:
• TEMPERATURE PLOT
• HUMIDITY  PLOT
• ANALOG SENSOR #1 PLOT
• ANALOG SENSOR #2 PLOT
• ANALOG SENSOR #3 PLOT
• ANALOG SENSOR #4 PLOT
• MODIFY PLOT SCALES
Six different data types are recorded for graphing: temperature, humidity, and four user defined ana-
log inputs. Each data type can be viewed over three different time scales and two different resolu-
tions. The three time scales are 90 minutes, 8 hours, and 24 hours. The two resolutions are minimum 
and maximum. With minimum resolution selected, the full scale of the sensor is displayed. In other 
words, the largest and smallest possible sensor readings are shown. Maximum resolution shows a 
range that covers two-fifths of the full scale sensor range. 
3.10.1 Modify Plot Scales
The MODIFY PLOT SCALES menu item adjusts the layout of the graph. This setup screen selects 
the time scale and resolution. It also adjusts the center of the graph for a maximum resolution graph.
The time scale and resolution can also be changed while the graph is displayed. The DOWN arrow key 
changes the time scale from 90 minutes, to 8 hours, to 24 hours. The UP arrow key toggles the display 
between maximum and minimum resolution.
NOTE
Power MUST be cycled off, then on, from the unit disconnect switch for the control system 
to update the DIP switch settings (except for switch 8).
Table 11
Setting options
Switch #
Off
On
1
No Part Coil
Part Coil/Chilled Water
2
Electric/Hot Gas Reheat
Hot Water Reheat
3
All
Not Used
4
No GLYCOOL
GLYCOOL
5
No Dual Cooling
Dual Cooling
6
Not Used
Not Used
7
a
Tight Control
Standard Control
a
SCR reheats only (with special software); otherwise, not used.
NOTE
The clock uses the 24 hour system (For example: 17:00 would be 5:00 PM). The date and time 
are backed up by battery.