Elkay HRC32W プリント

ページ / 2
97582C (01/21/2000)
HRC32W
1. This unit is intended for remote installation only. 
It is important to insure proper ventilation. A minimum of 6 inches
    (152mm) to the front must be maintained, and 6 inches (152mm) to the rear of the unit. 2. This chiller has been designed for use with potable water 
and includes an o-ring seal on the drain plug. This
    fitting should be replaced if the unit is to be used with more aggressive fluids. 3. Installer to provide air gap
 at condenser water outlet to comply with local plumbing specifications.
4. Connecting lines to be made of copper. 
Thoroughly flush all lines to remove all foreign matter before connecting to
    cooler. If flushing does not remove all particles, a water strainer should be installed in the supply line. 5. Connect cooler to building supply 
with a shut-off valve and install a union connection between the valve and the
    cooler. 6. Electrical:  Make sure power supply is identical
 in voltage, cycle, and phase to that specified on cooler serial plate.
    Never wire the compressor directly to the power supply.
HRC32W
Refrigeration Package
Installation Instructions
LEGEND
A
  =  3/8" O.D. TUBE W
A
TER INLET
B  =  3/8" O.D. TUBE W
ATER OUT
C  =  TEMPERA
TURE 
ADJUSTMENT
D  =  ELECTRICAL E  =  3/8" O.D. TUBE T
ANK DRAIN
F  =  3/8" O.D. TUBE CONDENSER W
ATER 
OUTLET
G  =  3/8" O.D. TUBE CONDENSER W
ATER 
INLET
INSTALLATION