2-40 HP Portable Chillers 
Chapter 6: Troubleshooting 
41 of 70 
Chapter 6:  Troubleshooting 
Problem 
Possible cause 
Solution 
No power. 
Check main disconnect, fuses, wiring, 
and power lead to unit. 
Wrong voltage supplied to unit. 
Voltage must be within plus or minus 
10% of nameplate rating. 
Defective on/off switch. 
Replace. 
Replace control circuit fuse. 
Check transformer. 
Control circuit fuse blown. 
Check for a short circuit. 
Defective control transformer. 
Replace. 
Piping flow switch circuit open. 
Add water or water/glycol solution as 
required. 
Unit does not run. 
Pump motor off on overload. 
Reset and test. 
High/Low thermostat set higher 
than temperature of liquid in 
system. 
Lower thermostat stage 1 set to 10°F 
(6°C) below the leaving temperature 
you want. 
Defective High/Low thermostat. 
Replace. 
Low refrigerant indicator on. 
Check refrigerant charge. 
Refrigerant low pressure switch 
contacts open. 
Sight glass should be clear and the 
moisture indicator should be green 
while compressor is running. Bubbles or 
foaming is normal when the hot-gas by-
pass solenoid is energized. Call for 
service if bubbling is occurring and/or 
moisture indicator is yellow. 
Clean the air filters. 
Check condenser fans for proper 
rotation. 
Check for dirty condenser. 
Refrigerant high-pressure indicator 
on.  
Reset and test. 
Fan motor out on overload. 
Reset and test. 
Defective fan cycling control. 
Replace. 
Defective fan motor. 
Repair or replace. 
Allow time to cool and reset, then check 
for high/low volt-age. It must be within 
plus or minus 10% of the nameplate 
rating. 
Compressor internal overload or 
fuses are open. 
Check for open fuses and loose 
compressor electrical connections. 
Compressor contactor holding coil 
open. 
Repair or replace. 
Defective pump motor to 
compressor auxiliary contact. 
Repair or replace. 
Pump runs; compressor does not. 
Broken wire in the compressor 
control circuit. 
Locate and repair.