Sterling A0554831 ユーザーズマニュアル

ページ / 70
2-40 HP Portable Chillers 
Chapter 7: Appendix 
55 of 70 
10 hp and 15 hp Remote Air-Cooled Portable Chillers 
Nominal operating parameters for remote air-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm 
per ton (9.1 lpm per 3.517 kW) with 95ºF (35ºC) ambient air. For 50 Hz applications, multiply capacity by 0.83. 
Nominal 60 Hz capacity flow rate must be maintained.
 
 
 
Nominal cooling  
Nom.  Com-
 
Refrigeration 
Power in amps 
e 
 capacity 
c tons 
water
pres- Nom.
connections 
460/3/60 
f 
HP 
no 
flow 
sor  pump
in. dia. ODS 
1 pump 
2 pumps 
 
pump pump pump 
gpm 
d
hp hp Discharge Liquid rated 
running 
rated running
10  9.9 9.5 9.4 23.8 10.0  2.0 
11/8” 
5/8”  22.5 18.2  24.2
19.9 
15  14.5 14.1 14.0  34.9 15.0  2.0 
11/8” 
5/8”  29.7 23.9  31.4
25.6 
c  Based on 50ºF (10ºC) chilled water supply temperature and 95ºF (35ºC) ambient air. Optional additional process 
pump hp reduces chiller capacity by 0.2 tons per hp (0.703 kW ref. cap. per 0.746 kW pump power). 
d  Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW), nominal 1 pump. 
e  An optional oversized process pump adds to the total rated or running chiller amperage. To find the new total 
chiller amperage, subtract the standard process pump amperage from the optional pump amperage (see Figure 1 
on page 16), and add it to the chiller rated or running amperage. 
f  Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages; multiply by 0.8 for 575/3/60 amperages. 
 
Remote air-cooled portable chillers come standard with mounting rails. Remote air-cooled portable 
chillers are charged with 25 psi (172.4 kPa/1.72 bars) nitrogen for shipping purposes. 
 
Com- 
Process connections, in. NPT 
Dimensions 
Weights 
pressor 
no pump,  1 pump, no
in inches 
c  
Dry 
Ship. d Oper. d e
hp 
pump  pumps  no tank  tank, to/from height width Depth
lbs. 
lbs. 
lbs. 
10.0 
1.5” 
2.0” 
1.5” 
1.5” / 2.0” 40.9” 
34.0” 
74.7”
827 1,052  1,159 
15.0 
2.0” 
2.5” 
2.0” 
2.0” / 3.0” 40.9” 
34.0” 
74.7”
870 1,095  1,202 
c  To convert to cm, multiply by 2.54. Add to height dimension based on mounting options. 
d Weight is for standard chiller. Some optional features will increase weight. 
e  Operating weight is with a full 40-gallon (151 liter) reservoir tank of water.