UTILITY SPECIFICATIONS REQUIRED – ELECTRIC 
Model 
Energy 
Power 
Voltage 
Current 
Phase 
Hz 
Recommended 
Electrical Specification 
Recommended 
Circuit Breaker 
Supply Wire 
Size 90° C 
Agency Listings 
1130/60 
Electric 
10kW 
120/208 VAC 
48 Amps 
60 Hz 
4 Wires, 2 Pole + N + G 
2 Pole, 50 Amp 
6 AWG 
UL, CSA, NSF 
1131/61 
Electric 
10kW 
120/240 VAC 
42 Amps 
60 Hz 
4 Wires, 2 Pole + N + G 
2 Pole, 50 Amp 
8 AWG 
UL, CSA, NSF 
1132/62 
Electric 
10kW 
120/208 VAC 
28 Amps 
60 Hz 
5 Wires, 3 Pole + N + G 
3 Pole, 30 Amp 
10 AWG 
UL, CSA, NSF 
1133/63 
Electric 
10kW 
120/240 VAC 
25 Amps 
60 Hz 
5 Wires, 3 Pole + N + G 
3 Pole, 30 Amp 
10 AWG 
UL, CSA, NSF 
1130-080-A 
Electric 
10kW 
120/208 VAC 
48 Amps 
60 Hz 
4 Wires, 2 Pole + N + G 
2 Pole, 50 Amp 
6 AWG 
UL, CSA, NSF 
1131/61-080-A 
Electric 
10kW 
120/240 VAC 
42 Amps 
60 Hz 
4 Wires, 2 Pole + N + G 
2 Pole, 50 Amp 
8 AWG 
UL, CSA, NSF 
1132/62-080-A 
Electric 
10kW 
120/208 VAC 
28 Amps 
60 Hz 
5 Wires, 3 Pole + N + G 
3 Pole, 30 Amp 
10 AWG 
UL, CSA, NSF 
1133-080-A 
Electric 
10kW 
120/240 VAC 
25 Amps 
60 Hz 
5 Wires, 3 Pole + N + G 
3 Pole, 30 Amp 
10 AWG 
UL, CSA, NSF 
1134 
Electric 
10kW 
380Y/208 VAC 
15 Amps 
50 Hz 
5 Wires, 3 Pole + N + G 
 
5 x 2.5mm
2
 
NSF 
1135 
Electric 
10kW 
415Y/240 VAC 
14 Amps 
50 Hz 
5 Wires, 3 Pole + N + G 
 
5 x 2.5mm
2
 
NSF 
1136 
Electric 
10kW 
240 VAC 
42 Amps 
50 Hz 
3 Wires, 1 Pole + N + G 
 
3 x 10.0mm
2
 
NSF 
1151 
Electric 
10kW 
200VAC 
29 Amps 
60 Hz 
4 Wires, 3 Pole + G 
 
3 x 4.0mm
2
 
NSF 
*1164-XXX-E 
Electric 
10kW 
400/230 VAC 
15 Amps 
50 Hz 
5 Wires, 3 Pole + N + G 
3 Pole, 32 Amp 
5 x 2.5mm
2
 
CE, NSF 
1130-000-A 
Electric 
10kW 
208 VAC 
48 Amps 
60 Hz 
3 Wires, 2 Pole + G 
2 Pole, 50 Amp 
6 AWG 
UL, CSA, NSF 
1131-000-A 
Electric 
10kW 
240 VAC 
42 Amps 
60 Hz 
3 Wires, 2 Pole + G 
2 Pole, 50 Amp 
8 AWG 
UL, CSA, NSF 
1132-000-A 
Electric 
10kW 
208 VAC 
28 Amps 
60 Hz 
4 Wires, 3 Pole + G 
3 Pole, 30 Amp 
10 AWG 
UL, CSA, NSF 
1133-000-A 
Electric 
10kW 
240 VAC 
25 Amps 
60 Hz 
4 Wires, 3 Pole + G 
3 Pole, 30 Amp 
10 AWG 
UL, CSA, NSF 
1130-08H-A 
Electric 
12kW 
208 VAC 
63 Amps 
60 Hz 
3 Wires, 2 Pole + G 
2 Pole, 90 Amp 
4 AWG 
UL, cUL, NSF 
1131-08H-A 
Electric 
12kW 
240 VAC 
54 Amps 
60 Hz 
3 Wires, 2 Pole + G 
2 Pole, 50 Amp 
6 AWG 
UL, cUL, NSF 
1132-08H-A 
Electric 
12kW 
208 VAC 
36 Amps 
60 Hz 
4 Wires, 3 Pole + G 
3 Pole, 70 Amp 
8 AWG 
UL, cUL, NSF 
1133-08H-A 
Electric 
12kW 
240 VAC 
31 Amps 
60 Hz 
4 Wires, 3 Pole + G 
3 Pole, 40 Amp 
10 AWG 
UL, cUL, NSF 
 
* REF MODEL NUMBER KEY 
UTILITY SPECIFICATIONS REQUIRED – GAS 
Model 
Energy 
Power 
Voltage 
Current 
Phase 
Hz 
Recommended 
Electrical Specification 
Recommended 
Circuit Breaker 
Gas 
Agency Listings 
1116 
Nat. Gas 
40,000 BTU 
120 VAC 
7 Amps 
60 Hz 
3 Wires, 1 Pole + N + G 
1 Pole, 15 Amp 
40,000 BTU at 7 inches, H
2
O column** 
CSA, NSF 
1117 
L.P. Gas 
40,000 BTU 
120 VAC 
7 Amps 
60 Hz 
3 Wires, 1 Pole + N + G 
1 Pole, 15 Amp 
40,000 BTU at 11 inches, H
2
O column** 
CSA, NSF 
1154 
Nat. Gas 
45 MJ 
240 VAC 
2 Amps 
50 Hz 
3 Wires, 1 Pole + N + G 
 
45 MJ/HR at 1.7 kPa, H
2
O column** 
AGA*, NSF 
1155 
L.P. Gas 
45 MJ 
240 VAC 
2 Amps 
50 Hz 
3 Wires, 1 Pole + N + G 
 
45 MJ/HR at 2.73 kPa, H
2
O column** 
AGA*, NSF 
1156 
Town 
45 MJ 
240 VAC 
2 Amps 
50 Hz 
3 Wires, 1 Pole + N + G 
 
45 MJ/HR at 3.6 kPa, H
2
O column** 
AGA*, NSF 
1157 
Nat. Gas 
40,000 BTU 
220/240 VAC 
2 Amps 
50 Hz 
3 Wires, 1 Pole + N + G 
 
40,000 BTU at 7 inches, H
2
O column** 
NSF 
1158 
L.P. Gas 
40,000 BTU 
220/240 VAC 
2 Amps 
50 Hz 
3 Wires, 1 Pole + N + G 
 
40,000 BTU at 11 inches, H
2
O column** 
NSF 
*1154-XXX-E 
Nat. Gas 
12kW 
230 VAC 
2 Amps 
50 Hz 
3 Wires, 1 Pole + N + G 
1 Pole, 16 Amp 
12 kW/HR at 17.4 mB, H
2
O column** 
CE, NSF 
*1155-XXX-E 
L.P. Gas 
12kW 
230 VAC 
2 Amps 
50 Hz 
3 Wires, 1 Pole + N + G 
1 Pole, 16 Amp 
12 kW/HR at 27.4 mB, H
2
O column** 
CE, NSF 
1116-000-A 
Nat. Gas 
40,000 BTU 
120 VAC 
7 Amps 
60 Hz 
3 Wires, 1 Pole + N + G 
1 Pole, 15 Amp 
40,000 BTU at 7 inches, H
2
O column** 
CSA, NSF 
1117-000-A 
L.P. Gas 
40,000 BTU 
120 VAC 
7 Amps 
60 Hz 
3 Wires, 1 Pole + N + G 
1 Pole, 15 Amp 
40,000 BTU at 11 inches, H
2
O column** 
CSA, NSF 
1116-080-A 
Nat. Gas 
40,000 BTU 
120 VAC 
7 Amps 
60 Hz 
3 Wires, 1 Pole + N + G 
1 Pole, 15 Amp 
40,000 BTU at 7 inches, H
2
O column** 
CSA, NSF 
1117-080-A 
L.P. Gas 
40,000 BTU 
120 VAC 
7 Amps 
60 Hz 
3 Wires, 1 Pole + N + G 
1 Pole, 15 Amp 
40,000 BTU at 11 inches, H
2
O column** 
CSA, NSF 
 
GAS PRESSURE CONVERSION CHART 
Inches of 
Water Column 
KPa 
m-Bar 
Millimeters of 
Water Column 
3.5 
0.87 
8.70 
88.9 
4.5 
1.12 
11.2 
114.3 
1.74 
17.40 
177.8 
10 
2.48 
24.87 
254.0 
10.5 
2.61 
26.11 
266.7 
11 
2.73 
27.36 
279.4 
14 
3.48 
34.81 
355.6 
14.5 
3.61 
36.05 
368.3 
* AGA – Australia Gas Association (See 1154 & 1155 above) 
 
** NOTE:  For proper operation, the gas valve requires a nominal inlet pressure of 7 inches of H
2
O for natural gas and 11 inches of H
2
O column 
for L.P. gas.  A minimum inlet pressure of 1.0 inch of H
2
O column above the manifold setting (NAT. manifold 3.5” H
2
O, L.P. manifold 10” H
2
O) 
must be maintained with no pressure drop from the no load to full load condition.  The maximum inlet pressure must be maintained at or below 
½ PSIG (14.5 inches H
2
O column).  Refer to the chart on the left for pressure conversions. 
 
Electrical Supply for Australia: 
Single Phase:  240 VAC, 50 Hz / 20 Amp; one neutral & one earth/ground. 
Three Phase:  240/415 VAC / 20 Amp; three active, one neutral & one earth/ground. 
 
All ovens require separate service and dedicated neutral. 
 
NOTE:  Do not install the (these) oven(s) in any area with an ambient temperature in excess of 95°F / 35° C.  Doing so will cause damage to the 