Impinger II – Advantage Digital Service Manual - Domestic 
3
SEQUENCE OF OPERATION 
IMPINGER II ADVANTAGE 
SERIAL NUMBER 2038616 AND ABOVE 
(OVENS WITH PUSH BUTTON CONTROLS) 
 
1130-000-A 
 208VAC 60 
HZ. 
 1 
PHASE 
1131-000-A 
 240VAC 60 
HZ. 
 1 
PHASE 
1132-000-A 
 208VAC 60 
HZ. 
 3 
PHASE 
1133-000-A 
 240VAC 60 
HZ. 
 3 
PHASE 
 
 
POWER SUPPLY 
Electrical power to be supplied to the oven by a three conductor service for single 
phase and a four conductor service for three phase. 
Black conductor is hot. 
Red conductor is hot. 
Orange conductor is hot (used for three phase only). 
Green conductor is ground. 
CONTROL BOX AUTO   
COOL DOWN 
When the temperature in the control box reaches 120
°F ± 3° (48.9°C ± 1.7°), the 
cooling fan thermostat will switch power to the control box cooling fan. The 
thermostat will interrupt power to the cooling fan when the control box 
temperature falls to 100
°F ± 3° (37.8°C ± 1.7°). 
MAIN FAN CIRCUIT 
Power is permanently supplied through the 10 amp fuses, through the normally 
closed control box hi-limit thermostat, to the normally open main power switch. 
Power is also supplied to the normally open cooling fan thermostat. Closing the 
main power switch supplies 208/240VAC to the main fan motor, the cooling fan 
motor, the primary of the control transformer, the conveyor motor and to the oven 
control. 
TEMPERATURE CONTROL 
Closing the main power switch supplies 208/240VAC to the primary of the control 
transformer. Secondary voltage, 24VAC, is supplied to the oven control. The oven 
control is set to desired temperature. The thermocouple will provide varying 
millivolts to the oven control. The oven control supplies 208/240VAC to the coil of 
the heater relay at intermittent intervals to maintain the desired temperature. The 
display on the oven control will indicate when the heater relay is energized. 
NOTE: The display also indicates oven temperature.   
CONVEYOR DRIVE 
Closing the main power switch supplies 208/240VAC to the conveyor motor and 
to the primary of the control transformer. Secondary voltage, 24VAC, is supplied 
to the oven control. Setting the oven control to the desired time outputs voltage, 
through a reversing switch, to the conveyor motor. 
NOTE: The conveyor system uses a hall effect sensor and magnet to prove 
operation of the conveyor motor. If the conveyor motor is not running, “BELT 
JAM” is indicated on the display.