Honeywell DR4300 ユーザーズマニュアル
Input and Output Calibration for Recorder with Display
12/03
DR4300 Circular Chart Recorder Product Manual
149
5.4.4 RTD (Resistance Temperature Detector) Inputs
Table 5-7 Set Up Wiring Procedure for Calibrating RTD Inputs
Step Action
1
Connect the copper wire to the calibration source (see Table 5-3).
2
Connect the other end of the copper wire to the TB2 terminals on the printed circuit assembly
for the input channel being calibrated.
for the input channel being calibrated.
Main PCA
Pen 2
Pen 2
Main PCA
Pen 1
Pen 1
7
TB2
TB1
7
TB2
TB1
TB2
+
R
–
-
+
Decade box
Copper
wires
24093
Figure 5-4 Calibration Set Up Diagram for RTD Inputs