L404F,T,V PRESSURETROL
®
 CONTROLLERS
71-2429—06
4
INSTALLATION
When Installing This Product…
1. Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous 
condition.
2. Check on the ratings given in the instructions and 
marked on the product to make sure the product is 
suitable for your application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out the product 
operation as provided in these instructions.
IMPORTANT
When making pipe connections, use pipe dope 
sparingly to seal the joints; any excess dope may clog 
the small hole in the fitting and prevent the controller 
from operating properly.
Location and Mounting (L404F)
Locate the L404F where the ambient temperature will not 
exceed 66°C (150°F). The L404F can be mounted near the 
pressure gauge, at a remote location, in a fitting provided by 
the boiler manufacturer, or in a special mounting on low water 
cutoffs. The L404F should always be mounted above the water 
line in steam boiler applications.
NOTE: For accurate operation, supplemental heat should be 
added to installations where temperatures fall below   
-29°C (-20°F).
A steam trap must be connected between the L404F and the 
boiler (see Fig. 2) to prevent boiler scale and corrosive vapors 
from attacking the elbows or diaphragm.
 
Fig. 2. Steam trap mounting.
Pressure Gauge Mounting
To mount beside a pressure gauge, remove the gauge, and 
install in its place the steam trap with a tee on top. Mount the 
PressureTrol
®
 unit and pressure gauge on the side of the tee 
by means of nipples and elbows (see Fig. 2).
Remote Mounting
Excessive vibration at the boiler may affect the operation of the 
L404F. In these cases, the L404F should be remotely located, 
subject to the following:
1. All piping must be suitable and properly pitched to drain 
all condensation back to the boiler.
2. The remote mounting must be solid.
3. A steam trap must be used at one end of the piping.
Boiler Mounting
If it is not convenient to mount the L404F adjacent to the 
pressure gauge, install a steam trap at the location 
recommended by the boiler manufacturer, then screw the 
device directly to the steam trap.
Location and Mounting (L404T,V)
Location
NOTE: For most accurate operation, supplemental heat 
should be added to installations where the 
temperature falls below -20°F (-29°C).These 
controllers can be mounted at any location in the oil 
supply line, depending on the application. Typical 
locations are shown in Fig. 3. The low oil pressure 
controller should be located upstream from the safety 
shutoff valve(s). In a downstream location, there 
would be zero pressure when the burner is not 
running and the safety shutoff valve(s) is (are) closed. 
This could prevent startup or require manual reset 
every time the burner is started. The high oil pressure 
controller should be located as near to the burner as 
possible.
Mounting
Mount the oil pressure controller directly on the main pipe. 
Insert a tee in the pipe line, and connect a pipe nipple of 
appropriate size to the tee (see Fig. 4). Screw the hexagonal 
fitting (1/4-18 NPT internal thread) of the pressure controller to 
the pipe nipple. To avoid leaks and damage to the case, use a 
parallel jaw wrench on the hexagonal fitting close to the pipe 
nipple. Do not tighten the pressure controller by hand by 
holding the case. 
Make all pipe connections in accordance with approved 
standards. Use only a small amount of pipe compound to seal 
the connection joints. Excess pipe compound may clog the 
orifice in the pipe fitting and prevent the controller from 
operating properly.
4-1/2 TO 5-1/2 
(114.3 TO 139.7) 
 
BOILER 
STEAM TRAP
(SIPHON LOOP)
TEE 
PRESSURE 
GAUGE 
PRESSURE 
CONTROLLER 
M23885 
1
1  1/4 IN. PIPE WITH 1/4 - 18 NPT EXTERNAL THREADS
ON BOTH ENDS AND 2-1/4 IN. DIAMETER LOOP.