Sun Microsystems FC-100 ユーザーズマニュアル
2-8
Sun StorEdge FC-100 Hub Installation and Service Manual • September 1998
2.3.8
Reassembling the Cabinet
Follow the instructions in your system or expansion cabinet documentation. If
necessary, be sure to:
necessary, be sure to:
■
Replace or close the top front panel
■
Replace or close the rear panel
■
Push the antitilt bar back into the cabinet
2.4
Troubleshooting
If a GBIC is properly installed, the Device Active LED for the GBIC should be on
and the Bypass LED should be off.
and the Bypass LED should be off.
If the Device Active LED for a GBIC is flashing, replace the GBIC.
If a GBIC is installed and the Device Active LED for the GBIC is off and the Bypass
LED is on, see
LED is on, see
.
TABLE 2-1
Troubleshooting
Possible Cause
Solution
Module not properly inserted
Remove and reinsert the GBIC.
Diminished or missing signal from node
Plug the optical cable from the other device
into a known good GBIC.
into a known good GBIC.
Bad hub port
Move the GBIC to a known good port on
the hub.
the hub.
Faulty GBIC
Replace the GBIC.