RuggedCom RS910L ユーザーズマニュアル

ページ / 29
10 
 
2007 RuggedCom Inc. All rights reserved 
 
Rev100
 
2.2.2  DC Power Supply Wiring and Grounding 
 
 
Figure 5 - DC Power supply wiring and grounding diagram 
 
The RS910L low voltage DC power supply features reverse polarity protection and dual 
independent inputs. The latter feature allows the connection of two DC sources with the same 
nominal voltage to provide redundant power supply inputs.  
 
The RS910L DC power supply inputs should be connected as follows: 
1.
  Connect to the DC inputs according to the polarity markings on the unit. 
2.
  Surge Ground should be connected to the Chassis Ground via a braided cable or other 
appropriate grounding wire. Surge Ground is used as the ground conductor for all surge 
and transient suppression circuitry internal to the unit. 
3.
  Chassis Ground must be connected to the protective earth. 
 
NOTES: 
1.
  Equipment must be installed according to the applicable country wiring codes. 
2.
  All line-to-ground transient energy is shunted to the Surge Ground terminal. In cases 
where users require the inputs to be isolated from ground, remove the ground braid 
between Surge and Chassis Ground. Note that all line-to-ground transient protection 
circuitry will be disabled.